| 2015-06-27 17:40:48 | 6/27/2015 |
| | PROJECT: 1300 MANGONIA DR. |
| | PERMIT#: 15040379 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) PROVIDE A RISER DIAGRAM AND A SITE PLAN INDICATING |
| | THE LOCATION OF THE MAIN DISCONNECT IN COMPLIANCE WITH |
| | NEC 230.70 |
| | THE INTENT OF THE CODE IS TO HAVE THE MAIN DISCONNECT |
| | AS CLOSE AS PRACTICABLE TO THE SERVICE ENTRANCE. THE |
| | RISER INDICATES A METER BY ITSELF AND A MAIN BREAKER |
| | PANEL IN CLOSE PROXIMITY. THE FLOOR PLAN INDICATES THE |
| | PANEL ON THE INSIDE OF THE HOUSE IN A HALLWAY. THE |
| | RISER NEEDS TO INDICATE COMPLIANCE WITH THE NEC 230.70. |
| | EITHER THE MAIN IS IMMEDIATELY NEXT TO THE METER OR THE |
| | MAIN BREAKER PANEL IS INSTALLED IN CLOSE ENOUGH |
| | PROXIMITY TO COMPLY WITH NEC 230.70. |
| | |
| | 2) PROVIDE A LOAD CALCULATION INDICATING THE 150AMP |
| | PANEL IS ADEQUATE FOR THE LOAD TO BE SERVED. NEC |
| | 408.30, NEC 220. |
| | THE HEATING VS COOLING LOAD IS NOT REPRESENTED |
| | ACCURATELY. REVISE ACCORDINGLY. |
| | |
| | 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 4) AT LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE PROVIDED AT OR |
| | NEAR THE EQUIPMENT REQUIRING SERVICING. NEC 210.70(3) |
| | |
| | 5) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO |
| | GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL |
| | EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR |
| | MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES. |
| | NEC 110.33(B) |
| | |
| | 6) PROVIDE A DISCONNECT FOR A/C AHU IN ATTIC SPACE |
| | ABOVE PANEL. NEC 440.14 |
| | |
| | 7) INDICATE THE LOCATION OF ALL REQUIRED SMOKE |
| | DETECTORS. FBC-RESIDENTIAL 314 AND 315 |
| | PROVIDE THE NAMES OF ALL ROOMS ON THE FLOOR PLAN. |
| | |
| | 8) INDICATE GFI PROTECTION ON RECEPTACLES WHERE |
| | REQUIRED. NEC 210.8 |
| | |
| | 9) INDICATE GFI PROTECTION WITHIN SIGHT OF MECHANICAL |
| | EQUIPMENT. NEC 210.63 |
| | OUTLETS STILL MISSING. |
| | |
| | 10) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 11) 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN ADDITION |
| | TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER |
| | PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH |
| | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| | |
| | 12) 210.52 (D) BATHROOMS. |
| | IN DWELLING UNITS, AT LEAST ONE RECEPTACLE OUTLET SHALL |
| | BE INSTALLED IN BATHROOMS WITHIN (3 FT) OF THE OUTSIDE |
| | EDGE OF EACH BASIN. |
| | THERE IS A BATHROOM SHOWN ON THE FLOOR PLAN WITH TWO |
| | BASINS. EACH BASIN REQUIRES A GFI RECEPTACLE TO BE |
| | INSTALLED WITHIN 3FT. |
| | |
| | 13) DISCONNECT REQUIRED FOR WATER HEATER. NEC 422.31 |
| | |
| | 14) INDICATE WHAT IS EXISTING TO REMAIN AND WHAT IS |
| | PROPOSED TO BE INSTALLED AS NEW. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |
| | |