| 2015-04-21 13:03:09 | 4/21/2015 |
| | PROJECT: PHOTOVOLTAIC SYSTEM 3121 WASHINGTON RD |
| | PERMIT#: 15040374 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE SITE PLAN INCLUDING THE FOLLOWING: WPB |
| | AMENDMENTS TO THE FBC 107.3.2 |
| | THE LOCATION HOUSE ON THE PROPERTY. |
| | THE LOCATION OF THE PHOTOVOLTAIC DC DISCONNECT / |
| | INVERTER ON THE HOUSE. |
| | THE LOCATION OF THE ELECTRICAL UTILITY METER ON THE |
| | HOUSE. |
| | THE LOCATION OF THE ELECTRICAL SERVICE PANEL ON OR IN |
| | THE HOUSE. |
| | |
| | 2) PROVIDE ALL SIGNAGE REQUIRED BY THE NEC 690 |
| | |
| | 3) INDICATE THE LOCATION OF EACH OF THE REQUIRED SIGNS |
| | IN RELATION TO THE NEW PHOTOVOLTAIC EQUIPMENT AND THE |
| | EXISTING ELECTRICAL EQUIPMENT. NEC 690 |
| | |
| | 4) PROVIDE MANUFACTURER PRODUCT APPROVALS ON EQUIPMENT |
| | INDICATING COMPLIANCE WITH LISTING REQUIRMENTS. NEC |
| | 690,4(D) |
| | |
| | 5) INDICATE A GROUNDING ELECTRODE DETAIL AT THE |
| | ELECTRICAL SERVICE AND INDICATE HOW THE SOLAR ARRAY |
| | GROUNDING ELECTRODE CONNECTS TO THE ELECTRICAL SYSTEM |
| | GROUNDING ELECTRODE SYSTEM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |