| 2015-04-24 13:31:51 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN | | | PRESSURES PURSUANT TO FBC-R301.2. THE WIND SPEED DESIGN | | | IS NOT CONSISTENT WITH THE ADOPTED MAP FBC 119, CITY | | | AMENDMENTS. THIS PROJECT IS LOCATED WITHIN 600 FEET OF | | | THE INTERCOASTAL WATERWAY. THE EXPOSURE CATEGORY IS D | | | AND THE WINDSPEED IS 170 MPH VULT. | | | | | | 2) SHEET S-1 INDICATES THAT THE ARRAY WILL BE MOUNTED | | | ON THE FLAT ROOF PORTION OF THE STRUCTURE WITH A .125 : | | | 12 SLOPE. THE CALCULATIONS ON SHEET S-2 INDICATE THE | | | SLOPE AS 5 : 12. PLEASE CLARIFY THE REASON THE 5 : 12 | | | SLOPE WAS USED. FBC 107.2.1 | | | | | | 3) SPECIFY THE TRIBUTARY AREA THAT WAS USED TO | | | DETERMINE THE POSITIVE AND NEGATIVE DESIGN WIND | | | PRESSURES. IT APPEARS THAT THE TRIBUTARY AREA PER | | | ATTACHMENT WOULD BE 10 SQFT. (WORST CASE) FBC-R301.2.1 | | | | | | IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | | ADDRESSED. | | | | | | |
|