| 2015-05-18 11:33:05 | 5/18/2015 THE OWNER CAME IN WITH AN ELECTRICIAN. THE |
| | ELECTRICIAN IS NOT THE QUALIFIER. I EXPLAINED TO BOTH |
| | OF THEM THAT I NEEDED TO SPEAK WITH THE QUALIFIER. THEY |
| | WERE BOTH ADVISED THE PROJECT FALLS OUTSIDE OF THE |
| | SCOPE OF THE CONTRACTOR?S LICENSE AND AN ENGINEER NEEDS |
| | TO BE INVOLVED. ONE PART OF THE SCOPE IS TO ADD A METER |
| | AND A MAIN IN THE ELECTRICAL ROOM TO FEED ONE OF THE |
| | SIX UNITS IN A SIX UNIT APARTMENT COMPLEX. I ASKED FOR |
| | A DESIGN OF THE ELECTRICAL SERVICE AND EXPLAINED THE |
| | STATUTORY LIMIT TO THE QUALIFIER?S SCOPE AND THEREFORE |
| | THE NEED FOR AN ENGINEERED DRAWING FOR THIS WORK |
| | |
| | FL SS 471.003 (H) ANY ELECTRICAL, PLUMBING, |
| | AIR-CONDITIONING, OR MECHANICAL CONTRACTOR WHOSE |
| | PRACTICE INCLUDES THE DESIGN AND FABRICATION OF |
| | ELECTRICAL PLUMBING, AIR CONDITIONING, OR MECHANICAL |
| | SYSTEMS RESPECTIVELY WHICH SHE OR HE INSTALLS BY VIRTUE |
| | OF A LICENSE ISSUED UNDER CHAPTER 489, UNDER PART I OF |
| | CHAPTER 553 OR UNDER ANY SPECIAL ACT OR ORDINANCE WHEN |
| | WORKING ON ANY CONSTRUCTION PROJECT WHICH: |
| | 1) REQUIRES AN ELECTRICAL OR PLUMBING OR AIR |
| | CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE OF |
| | $50,000.00 OR LESS; AND |
| | 2A) REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600AMPS |
| | (240VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL SYSTEM |
| | OR 800 AMPERES (240VOLTS) OR LESS ON A COMMERCIAL OR |
| | INDUSTRIAL ELECTRICAL SYSTEM; |
| | |