| Plan Review Notes For Permit 15040316 |
| Permit Number |
15040316 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-08-14 11:44:01 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED | | | BY THE OWNER/AGENT. 2010 FBC ENERGY CONSERVATION SECT. | | | 101.4.3 & 103.2 (SEE COMMENT # 7 FROM FIRST REVIEW) | | | | | | 2) PROVIDE A STRUCTURAL OVERHANG DETAIL AT THE GABLE | | | END RAKED BEAM THAT SPECIFIES THE FRAMING CONNECTORS | | | AND OTHER ATTACHMENT DETAILS. ALSO, SPECIFY THE LENGTH | | | OF THE OVERHANG. FBC-R 301.1 (SEE COMMENT # 10 FROM | | | FIRST REVIEW) | | | | | | 3) THE SLEEPING ROOM WINDOWS ARE REQUIRED COMPLY WITH | | | FBC-R 310 FOR EMERGENCY ESCAPE AND RESCUE OPENINGS. | | | FBC-R310.1.2 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL | | | BE 24 INCHES (610 MM). THE BEDROOM WINDOWS SPECIFIED IN | | | THE SCHEDULE ON SHEET 2 ARE 37-1/2" X 50-1/2" SINGLE | | | HUNG WINDOWS. THE NET CLEAR OPENING HEIGHT FOR THESE | | | WINDOWS IS LESS THAN 24". (SEE COMMENT # 3 FROM FIRST | | | REVIEW) | | | | | | 4) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | SINGLE HUNG WINDOWS (NOA NO. 13-0430.09) AND THE | | | ASPHALT ROOF SHINGLES (FL 10124-R15) ARE REQUIRED TO BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD. FBC 107.3.4 (SEE COMMENT # 11 FROM FIRST | | | REVIEW) | | | | | | | | | |
|