| Plan Review Notes For Permit 15040316 |
| Permit Number |
15040316 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-01 11:19:52 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) PROVIDE MANUAL J AC LOAD CALCULATIONS- SECTION | | | 403.6.1 FBC-10 ENERGY CONSERVATION. | | | 2) THE SUBMITTED ENERGY CALCULATION FORM IS OUTDATED. | | | THE HOUSE ADDITION WAS NEVER PERMITTED OR INSPECTED | | | UNDER EXPIRED #04070391, AND THEREFORE MUST BE APPROVED | | | UNDER THE CURRENT CODE IN EFFECT. PLEASE PROVIDE TWO | | | COPIES OF EITHER FORM 402-2010 OR FORM 405-2010- | | | SECTION 101.4.3 FBC-10 ENERGY. | | | 3) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN. | | | 4) PROVIDE CONDENSER MOUNTING PAD AND CONDENSER | | | TIE-DOWN DETAILS IN COMPLIANCE WITH SECTIONS | | | M1305.1.4.1 AND M1307.2.1 FBC-10 RESIDENTIAL. | | | 5) PROVIDE A CONDENSATE DISPOSAL PLAN: SHOW THE TYPE | | | AND SIZE OF CONDENSATE PIPING, PIPING RUN, AND DISPOSAL | | | LOCATION- SECTION M1411.3 FBC-10 RES. INDICATE A | | | SECONDARY OR AUXILIARY MEANS OF DISPOSAL- SECTION | | | M1411.3.1. | | | 6) INDICATE HOW RETURN AIR FROM THE 12X12 GRILL IN THE | | | HALLWAY IS RETURNING AIR TO THE AIR HANDLER. IS IT | | | BEING DUCTED? | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|