| Plan Review Notes For Permit 15040315 |
| Permit Number |
15040315 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-06-03 15:51:51 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | | FEE(S). | | | | | | 1) WHERE RECEPTACLES ARE INSTALLED WITHIN 6 FT OF THE | | | SINK SHALL BE GFI PROTECTED. NEC 210.8(5) | | | | | | 2) DISCONNECT REQUIRED FOR WATER HEATER. NEC 422.31 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|