| 2015-05-28 10:17:45 | BUILDING PLAN REVIEW |
| | MECHANICAL PLAN REVIEW |
| | W. P. B. PERMIT: 15040311 |
| | ADD: 111 S. SAPODILLA AVE. |
| | CONT: TURNER |
| | TEL: (786)229-4036 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. MAY 22/2015 |
| | ACTION: PROVISO |
| | |
| | BUILDING / MECHANICAL APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES |
| | |
| | REVISION IS REQUIRED BEFORE THE 1ST INSPECTION. PROVIDE |
| | ANCHORING DETAILS FOR THE ROOF TOP FAN, TO CURB, |
| | PROVIDE CURB DETAILS, PROVIDE CURB ANCHORING TO THE |
| | STRUCTURAL ROOF DECK. |
| | |
| | RULE 9N-3.31(D). |
| | 2010 FBC-B 1609.6.4.4.1 COMPONENTS AND CLADDING |
| | 2010 FBC-M 301.12 WIND RESISTANCE |
| | |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |