Plan Review Notes
Plan Review Notes For Permit 15040310
Permit Number 15040310
Review Stop M
Sequence Number 2
Notes
Date Text
2015-05-21 16:19:102ND MECHANICAL REVIEW
  
 1) SHEET MP-101: THE PREVIOUSLY REQUESTED WIND LOAD TIE
 DOWN ENGINEERING FOR THE CONDENSER PIPING CURB (KEY
 NOTE #4), AND THE OUTSIDE AIR INTAKE CURB (KEY NOTE
 #10)
 HAS NOT BEEN PROVIDED. PLEASE COMPLY.
 2) SHEET A-200: KEY NOTE #6 CALLS OUT NEW EXHAUST FAN
 AND CURB, HOWEVER THIS ITEM IS NOT SHOWN ON SHEET
 MP-101.
 REVISE THE SHEET AND NOTES ACCORDINGLY, PROVIDE A CUT
 SHEET FOR THE FAN, AND WIND LOAD TIE DOWN ENGINEERING.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  