Plan Review Notes
Plan Review Notes For Permit 15040310
Permit Number 15040310
Review Stop M
Sequence Number 1
Notes
Date Text
2015-04-25 09:11:46PLAN DENIED
 1) PROVIDE ENGINEER DETAIL ON THE PLAN SHOWING
 ALL NEW CURB TIE DOWN TO ROOF AND EQUIPMENT TIE DOWN
 TO CURB. PER SECTION 301.12 WIND RESISTANCE 2010 FBC
 (M)
 2) NOTE #10 PROVIDE DUCT SIZE, AND ENGINEERING ON DUCT
 AND CURB PER SECTION 301.12 WIND RESISTANCE
 3) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE.
 4) PROVIDE THE TYPE OF MATERIAL USED FOR CONDENSER
 WATER
 PIPING MUST MEAT TABLE 1202.4 AND 1202.5 ALSO PROVIDE
 ASTM
 LISTING ON PIPE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  