Plan Review Notes
Plan Review Notes For Permit 15040308
Permit Number 15040308
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-01 16:52:19THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
  
 THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008
 EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE
 APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND
 FLORIDA BUILDING CODE ENERGY CONSERVATION.
 1. HOWEVER SMALL IT MAY BE, ACCORDING TO THE 2008
 EDITION OF THE NEC, YOU SHALL SUBMIT A PANEL SCHEDULE
 ALONG WITH A LOAD CALC OF THE EXISTING SERVICE
 REFLECTING THE ADDED LOAD TO MAKE CERTAIN THAT THE
 EXISTING SERVICE IS CAPABLE OF ABSORBING THE ADDED
 LOAD.
 2. YOU SHALL ADHERE TO THE REQUIREMENTS OF THE FBC-R
 314 & 315 WHICHEVER IS APPLICABLE.
 3. LIGHTING IS REQUIRED IN THE LAUNDRY AREA, PER NEC
 210.70
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS
  
 FOR QUESTIONS ON THE ABOVE, PLEASE CONTACT:
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 PH: (561) 805-6743
 EMAIL: [email protected]
  