2015-06-08 17:16:06RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT AND
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THIS IS NOT A LEVEL 2 ALTERATION. THIS IS AN
 ADDITION. REVISE CODE ANALYSIS INFORMATION AS REQUIRED.
 SEC.401.4 OF 2010 FBC-EXISTING BUILDING.
  
 3- PROVIDE SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 HEATING REQUIREMENTS OF SEC. R303.8 OF 2010
 FBC-RESIDENTIAL.
  
 4- WALL SECTION ON SHEET 2:
 A) NEED TO SPECIFY MIN. 8D RING SHANK NAILS AS REQUIRED
 BY SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL. ALSO, NAIL
 SPACING AND ROOF ZONES ARE NOT CLEAR. WHAT'S 74" O.C.
 IN ZONE 3?
  
 B) SPECIFY ROOF SLOPE. SEC. R905.9.1 OF 2010
 FBC-RESIDENTIAL.
  
 C) ROOF VENTILATION: 4" X 24" VENT DOESN'T PROVIDE
 CROSS VENTILATION AS REQUIRED BY SEC. R806 OF 2010
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 D) SPECIFY 7/8" STUCCO THICKNESS AS REQUIRED BY TABLE
 R702.1(1) OF 2010 FBC-RESIDENTIAL.
  
 E) WHERE IS THE GABLE END BALLOON FRAMING SPECIFIED ON
 THE SECTION?. SEC. 107.2.1 CITY AMENDMENTS.
  
 F) SPECIFY WALL INSULATION. COORDINATE WITH THE ENERGY
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION
  
 G) REVISE ROOF INSULATION TO MATCH THE ENERGY
 CALCULATIONS. NOTE: ENERGY CALCULATIONS SUBMITTED
 REQUIRE R-30 INSULATION. R-30 BATT INSULATION DOESN'T
 FIT ON 2 X8 CEILING JOISTS. R-30 REQUIRES 9 1/2"
 INCHES. IN ADDITION INSULATION NEEDS TO ALLOW AT LEAST
 1 INCH OF SPACE FOR ROOF CROSS VENTILATION. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 H) SPECIFY CONNECTOR AT THE BASE OF THE WOOD STUDS.
 SEC. R601.2 OF 2010 FBC-RESIDENTIAL.
  
 I) SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR THE 1/2"
 ANCHOR BOLTS SPECIFIED TO FASTEN THE BOTTOM WOOD
 PLATES. SEC. R601.2 OF 2010 FBC-RESIDENTIAL.
  
 J) NEED TO SPECIFY ^" MIN. CLEARANCE FROM GRADE AS
 REQUIRED BY SEC. R404.1.6 OF 2010 FBC-RESIDENTIAL.
  
 K) NEED TO SPECIFY THE 12" MIN. DEPTH AS REQUIRED BY
 SEC. R403.1.4 OF 2010 FBC-RESIDENTIAL.
  
 L) NEED TO SPECIFY THE CONCRETE SLAB VAPOR BARRIER AS
 REQUIRED BY SEC. R405.2.2 OF 2010 FBC-RESIDENTIAL.
  
 5- ROOF FRAMING PLAN ON SHEET 2:
 A) SPECIFY ROOF SLOPE AS REQUIRED BY SEC. R905.9.1 OF
 2010 FBC-RESIDENTIAL.
  
 B) SPECIFICATIONS ON ROOF PLAN CALL FOR 2" X 8" JOISTS
 @ 24"O.C.. FLOOR PLAN DOESN'T SHOW 24" O.C. SPACING.
 REVISE AS REQUIRED. SEC107.2.1 CITY AMENDMENTS.
  
 C) GIVEN THE JOIST SIZE, SPACING AND SPAN SHOWN ON ROOF
 PLAN PROVIDE CALCULATIONS SHOWING THAT IS ADEQUATE FOR
 THE LOADS SPECIFIED ON SHEET 1 OF 2. OR PROVIDE TABLE
 THAT CONFIRMS LOADS BASED ON THE SIZE AND SPAN SHOWN ON
 PLANS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL AND SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 6- FRAMING DETAIL ON SHEET 2 OF 2 DOESN'T MATCH
 INFORMATION SHOW ON WALL SECTION "A". REVISE AS
 REQUIRED. ALSO, THERE ARE NOT EXISTING HEADERS. THIS IS
 AN ADDITION (NEW CONSTRUCTION). WHY THERE ARE NOT
 CRIPPLE STUDS FOR WINDOW FRAMING. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 7- ARCHITECT TO PROVIDE ALL HIS INFORMATION IN THE
 TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 F.S.
  
 8- ENERGY CALCULATIONS SUBMITTED:
 A) FORM 402-2010 IS INCOMPLETE. IS MISSING THE BOTTOM
 PART WHERE OWNER/AGENT NEEDS TO CERTIFY COMPLIANCE.
 PROVIDE FULL FORM SIGNED BY AND DATED BY THE
 OWNER/AGENT. SEC. 103.2.3.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING
 OWNER, PERMITTING OFFICE AND JURISDICTION #. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) ITEM # 10 REQUIRES R-30 INSULATION AS REQUIRED BY
 GENERAL INSTRUCTION #2. TABLE 402A REQUIRES R30 CEILING
 INSULATION. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 9- FLAT ROOF NOA 14-0611.01 SUBMITTED: PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION # 7 ON LAST PAGE OF NOA SUBMITTED. NEED THE
 CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 10-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS. PROVIDE THE FLORIDA PRODUCT
 APPROVAL COVER PAGE FOR DRAWINGS SUBMITTED. IF THERE IS
 NOT FLORIDA PRODUCT APPROVAL , THEN MANUFACTURER MAY
 APPLY FOR LOCAL PRODUCT APPROVAL.
  
 B) EXTERIOR SWING DOOR. PROVIDE THE FLORIDA PRODUCT
 APPROVAL COVER PAGE FOR DRAWINGS SUBMITTED. IF THERE IS
 NOT FLORIDA PRODUCT APPROVAL , THEN MANUFACTURER MAY
 APPLY FOR LOCAL PRODUCT APPROVAL.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 LIST THE FLORIDA PRODUCT APPROVAL NUMBER ON DRAWINGS
 NEXT TO THE SPECIFIED CONNECTOR.
  
 11- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT