Plan Review Notes
Plan Review Notes For Permit 15040303
Permit Number 15040303
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-04-09 15:08:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE SUBMITTED PLAN DID NOT PROVIDE SUFFICIENT
 INFOMATION AND DETAIL REGARDING THE PROPOSED FIRE LINE
 INSTALLATION.
  
 PLEASE PROVIDE SPECIFIC DETAIL AS TO WHERE THE
 INSTALLATION IS PROPOSED, THE LENGTH, THE DEPTH, TYPE
 AND SIZE OF PIPE, FITTINGS, ETC.
  
 NO SPEC SHEETS OR DIAGRAMS WERE PROVIDED.
  
 NO MANUFACTURE CUT SHEETS DETAIL WERE PROVIDED.
  
 NO PRODUCT/EQUIPMENT DETAIL WAS PROVIDED.
  
 NO FIRE HYDRANT DETAIL WAS PROVIDED.
  
 THE COST AMOUNT OF $15,000 APPEARS TO BE BELOW THE
 EXPECTED COST OF SUCH INSTALLATION. PLEASE PROVIDE COPY
 OF CONTRACT INDICATING THE AMOUNT.