| Plan Review Notes For Permit 15040273 |
| Permit Number |
15040273 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-29 15:56:57 | 4847 FRED GLADSTONE DRIVE | | | TRACKING ##15040273 | | | MASTER #12050519 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET E-M201: PER NFPA 101 SECTION 7.1.3.2.1, | | | PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT | | | ENCLOSURE ASSEMBLY SHALL BE LIMITED TO DOOR ASSEMBLIES | | | FROM NORMALLY OCCUPIED SPACES AND CORRIDORS, REQUIRED | | | EXIT DOOR OPENINGS, ELECTRICAL CONDUIT SERVING THE EXIT | | | ENCLOSURE, DUCTWORK AND EQUIPMENT NECESSARY FOR | | | INDEPENDENT STAIR PRESSURIZATION, WATER OR STEAM PIPING | | | NECESSARY FOR THE HEATING OR COOLING OF THE EXIT | | | ENCLOSURE, SPRINKLER PIPING, STANDPIPES, AND | | | PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE | | | CIRCUITS ARE INSTALLED IN METAL CONDUIT AND THE | | | PENETRATIONS ARE PROTECTED. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|