Text |
| 2015-04-24 14:27:22 | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15040265 |
| | ADD: 2808 N. AUSTRALIAN AVE. |
| | CONT: CLAY KOHLMEYER |
| | TEL: (561)694-1214 |
| | E-MAIL: CLAYKOHLMEYER.COM |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE JUNE 01, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. APRIL 24/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION STATES THE MANUFACTURED |
| | BUILDING THAT IS BEING SET UP AS A TEMPORARY OFFICE, |
| | PLEASE PROVIDE THE DATES IT OFFICE IS TO BE OCCUPIED. |
| | 108.1 GENERAL. THE BUILDING OFFICIAL IS AUTHORIZED TO |
| | ISSUE A PERMIT FOR TEMPORARY STRUCTURES AND TEMPORARY |
| | USES. SUCH PERMITS SHALL BE LIMITED AS TO TIME OF |
| | SERVICE, BUT SHALL NOT BE PERMITTED FOR MORE THAN |
| | 6MONTHS. |
| | |
| | PLEASE NOTE IF THE MODULAR BUILDING IS TO BE IN USE |
| | GREATER THAN 6 MONTHS, THEN CONFORMANCE WITH SECTION |
| | 2010 FBC-B 1809.4 DEPTH AND WIDTH OF FOOTINGS. |
| | THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED |
| | GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE |
| | APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL |
| | ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL |
| | BE 12 INCHES. |
| | |
| | 2) THE SITE PLANS DOES NOT SHOW THE STAIR NOR THE RAMP |
| | LOCATIONS, OR THE LANDINGS AT THE TOP AND BOTTOM OF THE |
| | RAMP. PLEASE SHOW COMPLIANCE WITH THE 2010 FBC-B |
| | 1010.6.2 WIDTH. THE LANDING SHALL BE AT LEAST AS WIDE |
| | AS THE WIDEST RAMP RUN ADJOINING THE LANDING. |
| | |
| | 1010.6.3 LENGTH. THE LANDING LENGTH SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM. |
| | |
| | 1010.6.4 CHANGE IN DIRECTION. WHERE CHANGES IN |
| | DIRECTION OF TRAVEL OCCUR AT LANDINGS PROVIDED BETWEEN |
| | RAMP RUNS, THE LANDING SHALL BE 60 INCHES BY 60 INCHES |
| | (1524 MM BY 1524 MM) MINIMUM. |
| | |
| | 2010 FBC- ACCESSIBILITY CODE: 405.7.4 CHANGE IN |
| | DIRECTION. |
| | RAMPS THAT CHANGE DIRECTION BETWEEN RUNS AT LANDINGS |
| | SHALL HAVE A CLEAR LANDING 60 INCHES (1525 MM) MINIMUM |
| | BY 60 INCHES (1525 MM) MINIMUM. |
| | |
| | 405.7.5 DOORWAYS. |
| | WHERE DOORWAYS ARE LOCATED ADJACENT TO A RAMP LANDING, |
| | MANEUVERING CLEARANCES REQUIRED BY 404.2.4 AND 404.3.2 |
| | SHALL BE PERMITTED TO OVERLAP THE REQUIRED LANDING |
| | AREA. |
| | |
| | 3) STATE APPROVED PLANS SHEET 1 OF 5 GENRAL NOTE # 20 |
| | INDICATES WHEN THIS UNIT IS LOCATED IN A WIND BORNE |
| | DEBRIS REGION THE WINDOWS REQUIRE PROTECTION, PLEASE |
| | INDICATE HOW CODE COMPLIANCE WILL BE MET? 2010 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS |
| | & CLADDING. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |