| 2015-07-08 11:27:25 | CONTRACTOR HAS NOT ADDRESSED ORIGINAL REVIEW DEFICIENCY |
| | COMMENTS. PLEASE READ AND COMPLY WITH ALL THE |
| | FOLLOWING: |
| | |
| | NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES |
| | THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR |
| | TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED |
| | (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A |
| | CODE VIOLATION. |
| | |
| | 1) INDICATE REQUIRED EXIT SIGNS ON THE FLOOR PLAN. |
| | ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY |
| | VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO |
| | REACH THE EXIT IS NOT READILY APPARENT TO THE |
| | OCCUPANTS. NFPA 101 SECTION 7.10.1.5.1 |
| | 2) INDICATE REQUIRED EMERGENCY ILLUMINATION. EMERGENCY |
| | LIGHTING SYSTEMS SHALL BE DESIGNED AND INSTALLED SO |
| | THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT, |
| | SUCH AS THE BURNING OUT OF A LAMP CANNOT LEAVE IN TOTAL |
| | DARKNESS ANY SPACE THAT REQUIRES EMERGENCY |
| | ILLUMINATION. NEC 700.16 |
| | 3) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN. THE |
| | BRANCH CIRCUIT FEEDING THE EMERGENCY LIGHTING SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. NEC 700.12 |
| | 4) PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT AND CIRCUIT |
| | MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS |
| | CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| 2015-07-01 19:37:43 | I TRIED CONTACTING MR. RAWLS FOR FURTHER EXPLANATION OF |
| | HIS DESIGN BUT VM WAS FULL. I DEFERRED THIS BACK TO |
| | DHAYES. |