| Date |
Text |
| 2015-07-23 10:33:33 | RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 RESIDENTIAL |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD) FOR IMPACT FEES ASSESSMENT. |
| | COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND |
| | DEVELOPMENT CODE. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 2-CLARIFY IF NEW PORCH IS GOING TO BE SCREENED OR NOT. |
| | ELEVATIONS DON'T SHOW THE SCREEN BUT FLOOR PLAN ON |
| | SHEET 2 OF 5 SAYS "SCREEN PORCH". PROVIDE COMPLETE |
| | DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION AND |
| | INSTALLATION OF THE SCREEN ENCLOSURE SHOWING COMPLIANCE |
| | WITH SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 3- NEW CODE ANALYSIS INFORMATION ON SHEET 1 OF 5: THIS |
| | IS NOT ALTERATION LEVEL 2. THIS IS AN ADDITION. REVISE |
| | AS REQUIRED. SEC. 407 OF 2010 FBC-EXISTING BUILDING. |
| | |
| | 4- FLOOR PLAN ON SHEET 2 OF 5: |
| | A) EGRESS FROM EXISTING BEDROOM IS GOING TO BE BLOCKED |
| | BY THE NEW PORCH ADDITION. NEED TO PROVIDE COMPLIANCE |
| | WITH THE EGRESS REQUIREMENTS OF SEC. R310 OF 2010 |
| | FBC-RESIDENTIAL. SPECIFY IF THERE IS AN EGRESS WINDOW |
| | ON THE SOUTH SIDE OF THE EXISTING BEDROOM. IF SO, THEN |
| | SPECIFY LOCATION SIZE AND TYPE OF WINDOW ON THE SOUTH |
| | SIDE.. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | B) SPECIFY CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| | EACH SLEEPING ROOM AS REQUIRED BY SEC. R315 OF 2010 |
| | FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ROOF SHINGLES. NOTE: THERE WERE TWO DIFFERENT |
| | PRODUCT APPROVALS SUBMITTED. FLORIDA PRODUCT APPROVAL |
| | FL10124-R14 AND MIAMI-DADE NOA 11-1122.04. CLARIFY |
| | WHICH ONE IS GOIN TO BE USED. ALSO, THERE IS A REVIEW |
| | AND APPROVE STAMP ON THE MIAMI-DADE NOA 11-1122.04. |
| | CLARIFY WHO REVIEWED AND APPROVED IT.. AND WHY THE |
| | DRAWINGS ARE NOT SIGNED AND SEALED BY THE SAME PERSON? |
| | |
| | B) PRECAST LINTELS SPECIFIED ON SHEET 3 OF 3. (REPEAT |
| | COMMENT). |
| | |
| | 6- PROVIDE THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1 |
| | CITY AMENDMENTS. PLANS ARE MISSING THE NAME OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. NOTE: COORDINATE |
| | ITEM #5 (A) ABOVE. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLESE REMOVE AND REPLACE ANY REVISED SHEET. SUBMIT |
| | OLD SET FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT. |
| | (561)805-6712 |
| | [email protected] |