Plan Review Notes
Plan Review Notes For Permit 15040239
Permit Number 15040239
Review Stop B
Sequence Number 1
Notes
Date Text
2015-05-20 14:46:03RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: 2010 RESIDENTIAL
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) FOR IMPACT FEES ASSESSMENT.
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.
  
 2-REVISE THE DESIGN PARAMETERS INFORMATION SHOWN ON
 SHEET 1 OF 5:
 A) THE CURRENT CODE IS 2010 FBC-RESIDENTIAL NOT 2001
 FBC
  
 B) THE BUILDING EXPOSURE CATEGORY IS "C" NOT "B".
 REVISE AS REQUIRED. SEC. R301.2.1.4 AND SEC.
 R301.2.1.4.2 OF 2010 FBC-RESIDENTIAL.
  
 C) BASIC WIND SPEED OF 140 MPH IS NOT THE RIGHT WIND
 SPEED UNDER THE CURRENT CODE 2010 FBC-RESIDENTIAL.
 REVISE AS REQUIRED. SPECIFY THE ULTIMATE WIND SPEED AND
 THE NOMINAL WIND SPEED AS REQUIRED BY SEC. R301.2.1.3
 OF 2010 FBC-RESIDENTIAL.
  
 D) SPECIFY THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 OF 2010 FBC-RESIDENTIAL.
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF THE SCREEN ENCLOSURE
 SHOWING COMPLIANCE WITH SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 3- FLOOR PLAN ON SHEET 2 OF 5:
 A) EGRESS FROM EXISTING BEDROOM IS GOING TO BE BLOCKED
 BY THE NEW SCREENED PORCH ADDITION. NEED TO PROVIDE
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. R310 OF
 2010 FBC-RESIDENTIAL.
  
 B) SPECIFY ATTIC ACCESS. SEC. R807 OF 2010
 FBC-RESIDENTIAL.
  
 C) SPECIFY CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH SLEEPING ROOM AS REQUIRED BY SEC. R315 OF 2010
 FBC-RESIDENTIAL.
  
 4- FOUNDATION PLAN ON SHEET 3 OF 5:
 A) CLARIFY SIZE OF FOOTING SPECIFIED. 18" X 8" ?. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) INFORMATION ON LINTEL DETAIL IS NOT CLEAR. LETTERING
 IS TOO SMALL AND IS NOT LEGIBLE. SEC. 107.2.1.4 CITY
 AMENDMENTS. AND, COORDINATE INFORMATION WITH TYP. WALL
 SECTION ON SHEET 5 OF 5. NOTE: THERE ARE NO WINDOW OR
 DOOR OPENINGS ON THE ENCLOSED PORCH. THE WALLS SHOWN ON
 THIS PLAN ARE FOR A 2'-8" LOW WALLS ONLY. THEY DON'T GO
 ALL THE WAY UP TO THE BOTTOM OF THE BEAM. PROVIDE CLEAR
 AND COMPLETE DETAILS AND SPECIFICATIONS FOR BEAM
 BETWEEN PORCH COLUMNS SHOWING COMPLIANCE WITH SEC.
 R601.2 OF 2010 FBC-RESIDENTIAL.
  
 5- ROOF PLAN ON SHEET 4 OF 5:
 A) TRUSS CONNECTOR (HETA 20) DOESN'T WORK FOR THE
 EXISTING WALL. IT CAN NOT BE EMBEDDED INTO THE EXISTING
 TIE BEAM. REVISE AS REQUIRED. SEC. R801.2 OF 2010
 FBC-RESIDENTIAL.
  
 B) STRAPPING SCHEDULE SPECIFIES CONNECTOR "TO CONCRETE
 BEAM" . WHERE IS THE CONCRETE BEAM. CLARIFY AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 6- TYPICAL WALL SECTION ON SHEET 5 OF 5:
 A) MOST OF THE INFORMATION IS NOT CLEAR. LETTERING IS
 TOO SMALL AND IS NOT LEGIBLE. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) REVISE ROOF SHEATHING NAILING SPECIFICATIONS. NEED
 TO USE MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1 OF 2010 FBC-RESIDENTIAL.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF THE SOFFIT TO SHOW
 COMPLIANCE WITH THE DESIGN PRESSURES AS REQUIRED BY
 SEC. R703.1.3 OF 2010 FBC-RESIDENTIAL.
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 PORCH CEILING CONSTRUCTION AND INSTALLATION. PROVIDE
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1.
 ALSO, PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 5/8 DRYWALL. TAKE INTO CONSIDERATION THAT THIS IS AN
 EXTERIOR APPLICATION.
  
 E) PROVIDE LEGIBLE AND CLEAR SPECIFICATIONS FOR THE
 BEAM. REMEMBER THAT THIS IS NOT A CONTINUOUS WALL. THIS
 IS AN ENCLOSED PORCH SUPPORTED ON COLUMNS. SEC. R801.2
 OF 2010 FC-RESIDENTIAL.
  
 F) COORDINATE INFORMATION ON TYP. WALL & BEAM
 ATTACHMENT DETAIL WITH TYP. WALL SECTION. COORDINATE
 BEAM SPECIFICATIONS AND THERE IS NOT CONCRETE BLOCK
 WALL. THEY ARE JUST COLUMNS AND BEAM. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 G) SPECIFY SIZE OF SOFFIT VENT TO SHOW COMPLIANCE WITH
 SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES.
  
 B) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 PROVIDE THE PRODUCT APPROVAL NUMBER NEXT TO THE
 SPECIFIED CONNECTOR OR PROVIDE COPY OF PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 C) PRECAST LINTEL SPECIFIED ON LINTEL DETAIL.
  
 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $13, 000. THE
 PERMIT FEE BALANCE IS $339.78.
  
 9- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLESE REMOVE AND REPLACE ANY REVISED SHEET.
 RESUBMIT OLD SET FOR REFERENCE.
  