| Plan Review Notes For Permit 15040207 |
| Permit Number |
15040207 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-04-20 12:59:11 | RESIDENTIAL (R3) ROOFING, FOURTH BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- NOA 10-0608.02 SUBMITTED IS FOR INSULATED ASSEMBLIES | | | ONLY ALSO. SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO | | | BE USED. TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES | | | OF SEC. R301.2.1.4 OF 2010 FBC-RESIDENTIAL. | | | NOTE: SELECTED APPROVED ASSEMBLY THAT IS LIMITED BY | | | GENERAL LIMITATION #9 CAN NOT BE USED IF THE DESIGN | | | PRESSURES DON'T MEET THE REQUIRED DESIGN PRESSURES. SEE | | | GENERAL LIMITATION # 9 ON LAST PAGE OF NOA SUBMITTED. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. NED THE RAS 117 CALCULATIONS TO MEET THE | | | DESIGN PRESSURES REQUIRED BY SEC. 301.2.1.4 OF 2010 | | | FBC-RESIDENTIAL. | | | | | | 3- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN | | | WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT | | | APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY | | | AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|