| Plan Review Notes For Permit 15040207 |
| Permit Number |
15040207 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-04-20 10:37:56 | RESIDENTIAL (R3) ROOFING, THIRD BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- NOA SUBMITTED IS FOR INSULATED ASSEMBLIES ONLY. | | | SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED. TO | | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | R301.2.1.4 OF 2010 FBC-RESIDENTIAL. | | | NOTE: SELECTED APPROVED ASSEMBLY THAT IS LIMITED BY | | | GENERAL LIMITATION #9 CAN NOT BE USED IF THE DESIGN | | | PRESSURES DON'T MEET THE REQUIRED DESIGN PRESSURES. SEE | | | GENERAL LIMITATION # 9 ON LAST PAGE OF NOA SUBMITTED. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 12-0418.02 SUBMITTED. NED THE RAS 117 CALCULATIONS TO | | | MEET THE DESIGN PRESSURES REQUIRED BY SEC. 301.2.1.4 OF | | | 2010 FBC-RESIDENTIAL. | | | | | | 3- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN | | | WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT | | | APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY | | | AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|