| 2015-04-13 17:36:05 | RESIDENTIAL (R3) ROOFING, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- I REVIEWED THE PROPOSED ASSEMBLY W-10 FROM FLORIDA | | | PRODUCT APPROVAL FL2920-R8. THIS ASSEMBLY IS GOOD FOR | | | -85PSF. ACCORDING TO NOTE # 5 ON PAGE 1 OF 6 OF | | | FL2920-R8 THIS ASSEMBLY CAN NOT BE USED BECAUSE IT | | | DOESN'T MEET THE DESIGN PRESSURES REQUIRED FOR THIS | | | HOUSE AND RATIONAL ANALYSIS IS NOT ALLOWED. THIS HOUSE | | | IS LOCATED IN EXPOSURE D. THE DESIGN PRESSURES FOR THE | | | PERIMETER AND CORNER AREAS ARE HIGHER THAN -85PSF. | | | | | | 2- DESIGNER OF RECORD NEED TO REVIEW AND APPROVE IN | | | WRITING (NOT SIGNING AND SEALING) THE SEALOFLEX PRODUCT | | | APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY | | | AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|