2015-04-22 15:28:46COURTESY REVIEW -
  
 SPOKE WITH FIRE - THEY AGREED THAT, WHILE THE BUILDING
 MAY NOT BE 180', IT CANNOT BE DETERMINED WITH CERTAINTY
 THAT THE BUILDING IS LESS THAN 160' DUE TO POSSIBLE
 VARIANCES IN FLOOR HEIGHTS ON FLOORS OTHER THAN THE ONE
 FLOOR MEASURED BY CONTRACTOR. EITHER REVISE PLAN TO A
 HEIGHT OF 180' OR PROVIDE DOCUMENTATION FROM A LICENSED
 PROFESSIONAL (SUCH AS A SURVEYOR) PROVIDING AN EXACT
 BUILDING HEIGHT.
  
  