| Plan Review Notes For Permit 15040196 |
| Permit Number |
15040196 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-05-12 13:57:05 | 3RD REVIEW. | | | | | | 1) PROVIDE AN ELECTRICAL PANEL SCHEDULE INDICATEING THE | | | OCPD AND WIRE SIZE FOR THE WATER HEATER CIRCUIT. NEC | | | 408.8 | | | ) PROVIDE A LOAD CALCULATION INDICATING THE CAPACITY OF | | | THE SERVICE AND PANEL(S) TO SUPPORT THE ADDITIONAL LOAD | | | OF THE NEW WATER HEATER. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|