| 2015-04-07 06:15:29 | 1) SUBMIT AN EXISTING FLOOR PLAN SHOWING THE LOCATION |
| | OF THE EXISTING WATER HEATER. WHAT WILL BE DONE WITH |
| | THE EXISTING PLUMBING AND ELECTRIC? WPB AMEND. TO 2010 |
| | FBC SEC. 107.2.1. |
| | 2) INDICATE THE OCCUPANCY OF THIS SPACE? WHAT TYPE OF |
| | BUSINESS IS CURRENTLY OCCUPYING THIS SPACE? FBC |
| | SEC.302. |
| | 3) INDICATE ON THE PLANS WHAT THESE SINKS WILL BE USED |
| | FOR? WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 4) WHERE IS THE VENT FOR THE EXISTING SINK? WPB AMEND. |
| | TO 2010 FBC SEC. 107.2.1. |
| | 5) SUBMIT A WATER RISER FOR REVIEW. SHOW ALL PIPE SIZES |
| | AND VALVES. |
| | 6) A CLEANOUT IS REQUIRED IN THE STACK FOR THE AIR |
| | ADMITTANCE VALVE. FPC SEC.708.3.4. |
| | 7) SHOW REQUIREMENTS FOR CONTROLLING THERMAL EXPANSION |
| | IN THE WATER SUPPLY SYSTEM PER THE 2010 FPC |
| | SEC.607.3.OF THE 2010 FPC. |
| | 8) SHOW THE WATER LINES ON THE PLAN VIEW. WPB AMEND. TO |
| | 2010 FBC SEC. 107.2.1. |
| | 9) ONE OF THE SINKS SHALL COMPLY WITH THE FL. |
| | ACCESSIBILITY CODE SEC.212.3, 305, 306, 309 & 606. SHOW |
| | THE REQD. CLEAR FLOOR SPACE, HEIGHTS, DIMENSIONS OF |
| | SINK, |
| | 10) INDICATE ON THE PLAN IF THE WATER HEATER IS BEING |
| | INSTALLED ABOVE OR BELOW THE EXISTING COUNTER. IF ABOVE |
| | THE CONTER ON A SHELF, A PAN AND PAN DRAIN SHALL BE |
| | INSTALLED IN ACCORDANCE WITH THE 2010 FPC SEC.504.7. |
| | 11) THE RELIEF LINE SHALL DISCHARGE IN ACCORDANCE WITH |
| | 2010 FPC SEC.504.6. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |