| 2015-05-11 07:59:22 | 5/11/2015 |
| | PROJECT: M/M BIKOFSKY |
| | PERMIT#: 15040181 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, THE DWELLING UNIT SHALL BE EQUIPPED WITH |
| | SMOKE ALARMS AS REQUIRED FOR NEW DWELLINGS. |
| | INDICATE THE REQUIRED SMOKE DETECTORS. IF THE REQUIRED |
| | SMOKE DETECTORS ARE EXISTING, INDICATE THAT THEY ARE |
| | EXISTING TO REMAIN IN LOCATIONS AS REQUIRED BY THE |
| | FBC-R 314, AND 315 FOR CARBON MONOXIDE DETECTORS IF |
| | |
| | 2) FBC-E 502.3.8 RECESSED LIGHTING. |
| | RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| | ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED AND UNCONDITIONED SPACES. |
| | |
| | 3) 210.52 (D) BATHROOMS. IN DWELLING UNITS, |
| | AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| | BASIN. |
| | 3A) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL. |
| | (A) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) |
| | THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL. (1) BATHROOMS |
| | 3B) NEC 210.11(C) |
| | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS. |
| | INDICATE THE REQUIRED 20AMP CIRCUIT AND GFI RECEPTACLES |
| | AS INDICATED IN THE NEC 210.52(D), NEC 210.52.8(A)(1) |
| | AND NEC 210.11(C). |
| | |
| | 4) NEC 210.12 |
| | ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED. |
| | |
| | 5) NEC 406.11 |
| | ALL NEW GENERAL PURPOSE RECEPTACLES MUST BE TAMPER |
| | RESISTANT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |