| 2015-08-19 16:14:35 | PASSED BY DAVID HAYES ON 8/14/15 |
| 2015-08-11 14:26:40 | 8/11/2015 |
| | PROJECT: A/V AT CONVENTION CENTER |
| | PERMIT#: 15040163 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 4TH ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) FEEDER SCHEDULE IDENTIFICATION NUMBERS HAVE BEEN CUT |
| | OFF FROM THE REVISED SHEET. |
| | |
| | 2) INDICATE THE SIZES OF THE DISCONNECTS AND OCPD ON |
| | THE PRIMARY AND SECONDARY SIDE OF EACH TRANSFORMER IN |
| | COMPLIANCE WITH NEC 450 |
| | |
| | 3) INDICATE THE SIZE AND TYPE OF ALL SPEAKER CABLING IN |
| | COMPLIANCE WITH THE EQUIPMEENT IT IS CONNECTED TO. |
| | |
| | 4) CLEARLIY IDENTIFY ALL EQUIPMENT AND PANEL LOCATIONS |
| | ON THE FLOOR PLAN. INDICATE THE SIZE AND TYPE OF |
| | CONDUIT AND WIRE BETWEEN EACH PEICE OF EQUIPMENT. THERE |
| | ARE SEVERAL CONDUITS AN SHEET E.02 THAT ARE NOT |
| | IDENTIFIED. |
| | |
| | 5) |
| | |
| | 6) |
| | |
| | 7) |
| | |
| | 8) . |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |