| Date |
Text |
| 2015-07-15 10:16:18 | 7/15/2015 |
| | PROJECT: AV UPGRADE AT CHRSTIAN CONVENTION CENTER 1610 |
| | PALM BEACH LAKES BLVD |
| | PERMIT#: 15040163 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) CLARIFY THE OVERALL SCOPE OF ELECTRICAL WORK. SHEET |
| | E.04 INDICATES TWO NEW 2000AMP SECTIONS OF SWITCHBOARD |
| | SECTIONS. THESE NEW SECTIONS APPEAR TO BE RESPONSIBLE |
| | FOR FEEDING PORTIONS OF THE NEW PANELS AND TRANSFORMERS |
| | PROPOSED TO BE INSTALLED AS A PART OF THE UPGRADE. |
| | 1A) INDICATE ON AN ELECTRICAL FLOOR PLAN THE LOCATION |
| | OF THE 4000AMP SERVICE DISTRIBUTION SWITCHBOARD AS WELL |
| | AS ALL OTHER ASSOCIATED ELECTRICAL EQUIPMENT . |
| | |
| | 2) ADDITIONAL DETAILED CLARIFICATION REQUIRED. CREATE |
| | AN ELECTRICAL PAGE TO INDICATE THE CIRCUITRY DIAGRAM |
| | FOR SHEET THE VIDEO WALLS DEPICTED ON PAGE A.08. WPB |
| | AMENDMENTS TO THE FBC 107.2.1 |
| | |
| | 3) INCLUDE THE REQUIRED WORKING ACCESS AND ILLUMINATION |
| | TO THE SPACE BEHIND THE VIDEO WALLS FOR SERVICING THE |
| | ELECTRICAL EQUIPMENT AS REQUIRED BY NEC 110.33(B) AND |
| | 110.34(D) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |