| 2015-04-07 14:59:58 | NO ELECTRICAL PLANS HAVE BEEN INCLUDED IN THIS | | | SUBMITTAL PACKAGE. AN ELECTRICAL APPLICATION WITH THE | | | DESCRIPTION HIGH AND LOW VOLTAGE WIRING FOR NEW SOUND | | | BOOTH AND SPEAKERS. PROVIDE COMPLETE ELECTRICAL PLANS | | | REQUIRED TO INDICATE COMPLIANCE WITH THE FBC AND THE | | | NEC | | | PROVIDE A FLOOR PLAN INDICATING LOCATIONS FOR THE | | | ELECTRICAL SERVICE, ELECTRICAL PANEL(S) SOUND BOOTH AND | | | SPEAKERS. LWPB AMENDMENTS TO FBC 107.3.2, NEC 110.26 | | | PROVIDE A PANEL SCHEDULE INDICATING ALL NEW CIRCUITS | | | FOR NEW SOUND BOOTH. NEC 408.4 | | | PROVIDE A LOAD CALCULATION THAT INCLUDES ALL EXISTING | | | PLUS ADDITIONAL BRANCH CIRCUITS REQUIRED FOR NEW SOUND | | | BOOTH EQUIPMENT. |
|