| 2015-05-27 12:36:07 | REVISED RAS 117 CALCULATIONS BUILDING REVIEW COMMENTS. | | | | | | 1- ENGINEER TO SPECIFY SELECTED ASSEMBLY. | | | 2- CONTRACTOR HIGHLIGHTED ASSEMBLY WITH ANCHOR SHEET | | | FASTENING OPTION #1 ON PAGE 6 OF 15 OF NOA 12-0716.18. | | | THE DESIGN PRESSURES FOR THIS ASSEMBLY IS -52.5 PSF. | | | THIS ASSEMBLY CAN NOT BE USED BECAUSE IT DOESN'T MEET | | | THE DESIGN PRESSURES FOR ZONE 1 AS SPECIFIED BY THE | | | ENGINEER. | | | 3- FASTENING CAN NOT BE LESS THAN 4 INCHES ON CENTER. | | | CALCULATIONS SHOW 3.8". THIS CONTRADICTS ENGINEER NOTE | | | "ALL FRACTIONS ROUNDED DOWN BUT KEEPING TO MIN 4" | | | SPACING". RAS 117 DON'T ALLOW SPACING LESS THAN 4". | | | 4- ACCORDING TO NOA SUBMITTED THE NAILS NEED TO BE | | | STAGGERED IN THE CENTER OF THE SHEET. ENGINEER TO | | | REVISE NAILING PATTERN AS REQUIRED. |
|