Plan Review Notes
Plan Review Notes For Permit 15040129
Permit Number 15040129
Review Stop B
Sequence Number 6
Notes
Date Text
2015-09-17 14:53:479/17/15 RESPONDED E-MAIL TO SAM MALO.
  
 GOOD AFTERNOON,
 THE ENERGY CODE REQUIRES R19 MIN. IF YOU HAVE ENOUGH
 ROOM IN THE 2X10 ROOF JOIST FOR CROSS VENTILATION, THEN
 I DON'T SEE ANY PROBLEM. CHECK THE DIMENSION OF THE R20
 INSULATION.
 REGARDS,
  
 FROM: "SAM MALO"
 TO: ,
 DATE: 09/17/2015 12:24 PM
 SUBJECT: GARTH IVEY RES. 15040129
  
 GOOD AFTERNOON MR. GOMEZ,
 ?
 I SPOKE TO LISA SMITH, WHO PREPARED THE ENERGY CALCS.
 TO SEE IF WE USED R-20 IN THE "FLAT" ROOF AREA, TO
 ALLOW ADEQUATE CLEARANCE FOR VENTILATION, AND HOW THIS
 WOULD AFFECT THE CALCULATIONS. SO FAR, THIS DOESN'T
 SEEM TO BE AN ISSUE, SINCE THE ROOF AREA IS ONLY ~400
 SF, THE CALCS. STILL PASS.
 WOULD THIS BE ACCEPTABLE TO YOU?
 ?
 THANK YOU,
 SAM MALO
  
 ?
  
 ***BELOW ARE THE COMMENTS FOR THIRD REVIEW.
  
 ***NOTE: THE BUILDING REVIEW MAY BE APPROVED WITH A
 PROVISO. A PROVISO MEANS THAT THE COMMENTS BELOW WILL
 BE ADDRESSED AFTER THE PERMIT IS ISSUED. REVISSION FEES
 WILL APPLY.
 OWNER TO ADVICE IS PROVISO IS PREFERRED OR IF
 RE-SUBMITTING PAPERWORK TO ADDRESS THE COMMENTS BEFORE
 PERMIT IS ISSUED.
  
  
 RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
 (***NOTE: PLEASE MAKE SURE ENERGY CALCULATIONS ARE
 COORDINATED WITH PLANS AND ALL THE FORMS ARE COMPLETE
 AND SIGNED BY ALL PARTIES TO AVOID UNNECESSARY DELAYS.
 REPEAT COMMENT. ENERGY CALCULATIONS AND PLANS WERE NOT
 COORDINATED).
  
 A) CONDITIONED FLOOR AREA SHOWN ON ITEM #6 DOESN'T
 MATCH PLANS SUBMITTED. REVISE AS REQUIRED TO MATCH.
 SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) R-VALUE SHOWN ON ITEM #9 DOESN'T MATCH PLANS. REVISE
 AS REQUIRED TO MATCH. SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) CEILING TYPES AND AREA SHOWN ON ITEM #10 DON'T MATCH
 PLANS. ENGINEER SHOWS VENTED ATTIC (PITCHED AND FLAT
 ROOFS) AND THE SQUARE FOOTAGE DOESN'T MATCH PLANS.
 REVISE AS REQUIRED TO MATCH. SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 D) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS
 REQUIRED BY SEC. 103.2.3.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 IMPORTANT: LABEL WILL BE REQUIRED SHOWING THE DOORS AND
 WINDOWS U-FACTOR AND SHGC FACTOR SPECIFIED ON ITEM #7 .
 THIS IS REQUIRED WHEN ENERGY CALCULATIONS DON'T USE THE
 DEFAULT FACTOR.
  
 2- DESIGN PRESSURES WERE CHANGED ON THE WINDOW AND DOOR
 SCHEDULES ON SHEET 5.0. THE REVISE DESIGN PRESSURES
 DON'T CORRESPOND TO EXPOSURE "C". REVISE THE DESIGN
 PRESSURES ACCORDING TO THE WINDOW/DOOR SIZE AND
 LOCATION. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) MODIFIED BITUMEN FOR THE FLAT ROOF. AND CLEARLY
 IDENTIFY APPROVED ASSEMBLY. ALSO, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF 2010 FBC-RESIDENTIAL.
 ***RESPONSE: FLORIDA PRODUCT APPROVAL SUBMITTED
 FL1654-R9 WAS REVISED. NEED TO PROVIDE CURRENT FLORIDA
 PRODUCT APPROVAL REVISION #14. ALSO, NEED TO MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 DESIGN PRESSURES. SIGNED AND SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES.
 (NOTE: MAKE SURE ALL PRODUCT APPROVALS ARE FOR THE 2010
 CODE VERSION).
  
 ****REPEAT COMMENT. NOT ADDRESSED.
  
 B) VENTED HARDIE SOFFIT AS SPECIFIED ON SHEET 4.2. NOA
 15-0122.04 SUBMITTED DOESN'T INCLUDE VENTED SOFFITS.
 NOTE: ENGINEER TO SPECIFY SIZE OF VENTS TO SHOW
 COMPLIANCE WITH SEC. R806.
  
 4- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS INCLUDING
 THE PEEL & STICK SHINGLES UNDERLAYMENT SPECIFIED ON
 SHEET 4.2. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- CLARIFY WHY THERE ARE TWO DIFFERENT PRODUCT
 APPROVALS SUBMITTED FOR THE OVERHEAD GARAGE DOORS,
 SHINGLES RIDGE VENTILATION AND ROOF SHINGLES. CLEARLY
 IDENTIFY WHICH ONE IS GOING TO BE USED TO AVOID
 CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 6- STATIC ROOF LOUVER NOA 12-0809.01 SUBMITTED:
 ENGINEER TO REVIEW APPROVED APPLICATIONS ON PAGE 3 OF 4
 OF NOA 12-0809.01 SUBMITTED. THEN ENGINEER'S PROPOSED
 INSTALLATION ON SHEET 4.3 DOESN'T COMPLY WITH THE
 APPROVED APPLICATIONS. REVISE AS REQUIRED OR PROVIDE
 COMPLETE ENGINEER ANALYSIS SHOWING ALTERNATIVE
 COMPLIANCE. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 7- ENGINEER TO REVISE THE ROOF VENTING DETAIL ON SHEET
 4.3. THERE IS NOT 2" AIR GAP ON 2X10 ROOF RAFTERS WHEN
 INSTALLING R-30 INSULATION AS SHOWN ON DETAIL S2/4.2.
 KEEP IN MIND THE ACTUAL SIZE OF THE 2X10 AND THE
 THICKNESS OF R-30. REVISE AS REQUIRED. SEC. R806 OF
 2010 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE AND REMOVE ANY REVISED SHEET.. SUMIT
 OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  