Plan Review Notes For Permit 15040129
Permit Number 15040129
Review Stop B
Sequence Number 4
Notes
Date Text
2015-08-06 08:58:208/6/15 RECEIVED ANOTHER E-MAIL FROM SAM MALO REGARDING
 THE ROOF VENTILATION ITEM #11:
  
 ****RESPONSE:
 THERE IS NO INFORMATION FOR THE CROSS VENTILATION FOR
 THE FLAT ROOFS. ATTIC VENTILATION CALCULATIONS SHOWN
 ONLY ADDRESSES THE PITCHED ROOFS. ARE THE PITCHED ROOFS
 INTERCONNECTED SO THE AIR FLOW FROM ONE ROOF TO THE
 OTHER?. SEE AREA WHERE THE EXISTING MAIN ROOF RECEIVES
 THE NEW ROOF FOR THE GARAGE ADDITION. IS THE ROOF
 SHEATHING OF THE EXISTING MAIN ROOF GOING TO BE REMOVED
 OR THE NEW ROOF TRUSSES ARE LAYING ON THE ROOF
 SHEATHING?. PROVIDE COMPLETE SECTION/DETAIL SHOWING THE
 PROPOSED CONSTRUCTION AT THIS AREA. THE CODE
 REQUIREMENT IS TO PROVIDE CROSS VENTILATION FOR ENTIRE
 ROOF INCLUDING THE FLAT ROOFS. PLEASE COORDINATE WITH
 THE ENGINEER OF RECORD. CAREFULLY REVIEW THE ROOF PLAN
 WITH HIM, ADDRESS THE CROSS VENTILATION CODE ISSUE AND
 RESUBMIT REVISED PLANS. I APOLOGIZE BUT NO MORE PARTIAL
 REVIEWS WILL BE DONE UNTIL PLANS ARE SUBMITTED FOR FULL
 REVIEW. TO BE FAIR TO THE OTHERS, I NEED TO DO THE
 REVIEW ON PLANS THAT ARE ALREADY SUBMITTED AND WAITING
 ON LINE. I THINK MY COMMENT IS VERY CLEAR. IF YOU THINK
 YOU NEED MORE CLARIFICATION ON THIS ISSUE, PLEASE
 CONTACT STEVE KENNEDY, MY SUPERVISOR AT (561)805-6712
 OF [email protected].
 SINCERELY,
  
  
  
  
  
  
 RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- ENERGY CALCULATIONS SUBMITTED ARE DONE FOR A
 PROPERTY IN FORT PIERCE. REVISE ALL THE INFORMATION ON
 TOP OF FORM AS REQUIRED, AND, INCLUDE THE BUILDER'S
 NAME. SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
 REVIEW OF THE ENERGY CALCULATIONS WILL BE DONE WHEN
 CORRECT INFORMATION IS SUBMITTED.
 ***NOTE: PLEASE MAKE SURE ENERGY CALCULATIONS ARE
 COORDINATED WITH PLANS AND ALL THE FORMS ARE COMPLETE
 AND SIGNED BY ALL PARTIES TO AVOID UNNECESSARY DELAYS.
  
 2- THE PROJECT NAME SHOWN ON PLANS SUBMITTED IS
 CHAMBERS RESIDENCE. THIS DOESN'T MATCH THE NAME OF THE
 OWNER. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
 ***RESPONSE: SOME SHEETS STILL HAVE THE WRONG NAME.
 REVISE AS REQUIRED.
  
 3- SHEET 3.0 SPECIFIES REMOVAL OF WINDOWS AND DOORS.
 CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 (SPECIALLY THE BEDROOM WINDOWS) TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 604 OF 2010
 FBC-EXISTING BUILDING.
 ****RESPONSE: CLEARLY SPECIFY THE ACTUAL SIZE OF THE
 EXISTING WINDOW AND ACTUAL SIZE OF THE PROPOSED WINDOW.
 SIZES SHOWN ON SHEET 6.0 AND WINDOW SCHEDULE ON SHEET
 5.0 ARE NOT SHOWN ON THE PRODUCT APPROVAL SUBMITTED.
 (EGRESS WINDOWS SPECIFIED ON THE WINDOW SCHEDULE DON'T
 COMPLY WITH EGRESS).
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WOOD ENTRY DOOR AS SPECIFIED ON DOOR SCHEDULE.
 ***RESPONSE: FLORIDA PRODUCT APPROVAL FL15213-R1
 SUBMITTED IS FOR "FIBERGLASS DOOR" WITH WOOD DOOR
 FINISH. IS NOT A SOLID WOOD DOOR. PROVIDE PRODUCT
 APPROVAL FOR WOOD DOOR OR REVISE DOOR SCHEDULE TO MATCH
 PRODUCT APPROVAL.
  
 B) DINING ROOM EXTERIOR DOOR AS SHOWN ON PLANS AND DOOR
 SCHEDULE.
 ***RESPONSE: FLORIDA PRODUCT APPROVAL FL15213-R1
 SUBMITTED IS FOR "FIBERGLASS DOOR" WITH WOOD DOOR
 FINISH. IS NOT AN ALUMINUM SOLID DOOR. PROVIDE PRODUCT
 APPROVAL FOR ALUMINUM DOOR OR REVISE DOOR SCHEDULE TO
 MATCH PRODUCT APPROVAL.
  
 C) STORAGE DOUBLE DOOR AS SHOWN ON PLANS.
 ***RESPONSE: FLORIDA PRODUCT APPROVAL FL15213-R1
 SUBMITTED IS FOR "FIBERGLASS DOOR" WITH WOOD DOOR
 FINISH. IS NOT AN ALUMINUM SOLID DOOR. PROVIDE PRODUCT
 APPROVAL FOR ALUMINUM DOOR OR REVISE DOOR SCHEDULE TO
 MATCH PRODUCT APPROVAL.
  
 D) MODIFIED BITUMEN FOR THE FLAT ROOF. AND CLEARLY
 IDENTIFY APPROVED ASSEMBLY. ALSO, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF 2010 FBC-RESIDENTIAL.
 ***RESPONSE: FLORIDA PRODUCT APPROVAL SUBMITTED
 FL1654-R9 WAS REVISED. NEED TO PROVIDE CURRENT FLORIDA
 PRODUCT APPROVAL REVISION #14. ALSO, NEED TO MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 DESIGN PRESSURES. SIGNED AND SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES.
 (NOTE: MAKE SURE ALL PRODUCT APPROVALS ARE FOR THE 2010
 CODE VERSION).
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS AND ALL DETAILS. NOTE: PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO THE SPECIFIED CONNECTOR.
 ***RESPONSE: (REPEAT COMMENT NOT ADDRESSED. THERE WAS
 ONLY ONE LETTER SUBMITTED FROM SIMPSON-STRONG-TIE.
 (THAT'S NOT A PRODUCT APPROVAL. THE LETTER DOENS'T
 APPLY TO THIS JOB AND IS NOT VALID WITHOUT COMPLETE
 ENGINEERING CALCULATIONS).
  
 K) HARDIE BOARD SIDING AS SPECIFIED ON PLANS.
 ***RESPONSE: REVISED WALL SECTIONS SPECIFY STUCCO,
 WHILE EXTERIOR ELEVATIONS SPECIFY HARDIE SIDING. REVISE
 ALL DRAWINGS AS REQUIRED TO MATCH.
  
 L) HARDIE SOFFIT AS SPECIFIED ON PLANS/SECTIONS.
 ***RESPONSE: (REPEAT COMMENT).
  
 M) CLARIFY WHY SUBMITTING MIAMI-DADE NOA 11-1114.04 FOR
 HORIZONTAL SLIDING WINDOWS. WINDOW SCHEDULE DOESN'T
 SPECIFY THIS TYPE OF WINDOW. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 N) NEW COMMENT. PROVIDE PRODUCT APPROVAL FOR THE RIDGE
 VENT AND GOOSE-NECK VENTS AS SPECIFIED BY THE ENGINEER
 ON SHEET 4.3.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 ***RESPONSE: (REPEAT COMMENT NOT ADDRESSED. PRODUCT
 APPROVALS DON'T HAVE THE ENGINEER'S REVIEW STAMP OR ANY
 OTHER METHOD THAT SHOWS IN WRITING THAT THE ENGINEER
 REVIEWED THE PRODUCT APPROVALS. EACH PRODUCT APPROVAL
 NEED TO BE CLEARLY IDENTIFIED AS REVIEWED).
  
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 ROOF CROSS VENTILATION AS REQUIRED BY SEC. R806 OF 2010
 FBC-RESIDENTIAL FOR PITCHED AND FLAT ROOFS. IF
 DESIGNING UNVENTED ATTIC , THEN PROVIDE COMPLETE
 SPECIFICATIONS. SEC. R806.4
 ***RESPONSE: ROOF FRAMING PLAN ON SHEET 4.3 ONLY
 PROVIDE INFORMATION FOR THE PITCHED ROOFS. THERE IS NOT
 INFORMATION FOR THE FLAT ROOF. ALSO, PROVIDE COMPLETE
 DETAILS AND SPECIFICATIOS FOR THE RIDGE VENT AND
 GOOSE-NECK VENTS. PROVIDE CALCULATIONS FOR THE CROSS
 VENTILATION AND SIZES OF ALL VENTS.
  
 12- REVISED WALL SECTIONS SPECIFY STUCCO FINISH. STUCCO
 THICKNESS IS 7/8" MIN NOT 3/4". REVISE ALL DETAILS AS
 REQUIRED. TABLE R702.1(1).
  
 13- WOOD TRUSS DESIGN LOADS ON SHEET 4.3: SPECIFY THE
 ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2010
 FBC-RESIDENTIAL.
 ***RESPONSE: REVISE LOADS ON SHEET 4.0. THERE IS A PULL
 DOWN STAIR. SEE NOTE "G" OF TABLE R301.5.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE AND REMOVE ANY REVISED SHEET.. SUMIT
 OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT