2015-07-17 11:32:02ELECTRICAL PLAN REVIEW
  
 SECOND REVIEW FAILED AS INDICATED BELOW:
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED TO THE
 ELECTRICAL SUBMITTAL FOR A SATISFACTORY ELECTRICAL
 REVIEW:
  
 1.PER NEC 220.16, YOU SHALL PROVIDE LOAD CALCS FOR THE
 NEW LOAD CENTER.
 2. PER NEC 408.4, YOU SHALL PROVIDE A CIRCUIT DIRECTORY
 A/K/A PANEL SCHEDULE.
 3. INDICATE THE FEEDERS CONDUCTORS FOR THE NEW LOAD
 CENTER. SHALL BE IN ACCORDANCE TO THE RESULTS OF THE
 CONNECTED LOAD.
 4. YOU SHALL INDICATE THE FOLLOWING WITH EITHER A NOTE
 OR SHOWN ON THE PLANS:
 ALL OUTDOOR RECEPTACLES SHALL BE RATED AS WEATHER
 RESISTANT AS PER NEC 406.8
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT AS PER NEC
 406.11
 ARC-FAULT PROTECTION IS REQUIRED AS PER NEC 210.12
 LIGHTING OUTLET BOXES IN THE CEILING SHALL BE CAPABLE
 OF SUPPORTING 50#'S AS PER NEC 314.27
 5. BEDROOM HALL SMOKE DETECTOR SHALL ALSO BE CAPABLE OF
 DETECTING HIGH LEVELS OF CO (CARBON MONOXIDE) AS PER
 FBC-R 315.
 6.RELOCATE THE LIGHT OUTLET AT THE REAR DOORS SO AS NOT
 TO BLOCK IT BEHIND THE DOOR.
 7. OUTLETS SPACING THROUGHOUT ALL HABITABLE ROOMS SHALL
 BE AS INDICATED BY NEC 210.52(A)
 8. OUTLETS ALONG THE KITCHEN COUNTER SHALL BE AS PER
 NEC 210.52(C)
 9. MASTER BATHROOM OUTLET SHALL BE AS INSTRUCTED BY NEC
 210.52(D)
 10. THE MASTER BEDROOM CORRIDOR IS MISSING AN OUTLET AS
 PER NEC 210.52(H)
 11. CLARIFY THE DELTA 1 CLOUD WITH REGARDS TO WHAT USED
 TO BE HVAC EQUIPMENT IN THE FIRST REVIEW. KEEPING IN
 MIND THAT NEC 110.33(B) HAS SPECIFIC REQUIREMENTS WHICH
 SHALL BE ADDRESSED/CONSIDERED.
  
 FOR QUESTIONS, PLEASE CONTACT MIKE ALBARRAN
 CITY OF WEST PALM BEACH ELECTRICAL PLANS EXAMINER