| 2015-07-17 11:32:02 | ELECTRICAL PLAN REVIEW |
| | |
| | SECOND REVIEW FAILED AS INDICATED BELOW: |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED TO THE |
| | ELECTRICAL SUBMITTAL FOR A SATISFACTORY ELECTRICAL |
| | REVIEW: |
| | |
| | 1.PER NEC 220.16, YOU SHALL PROVIDE LOAD CALCS FOR THE |
| | NEW LOAD CENTER. |
| | 2. PER NEC 408.4, YOU SHALL PROVIDE A CIRCUIT DIRECTORY |
| | A/K/A PANEL SCHEDULE. |
| | 3. INDICATE THE FEEDERS CONDUCTORS FOR THE NEW LOAD |
| | CENTER. SHALL BE IN ACCORDANCE TO THE RESULTS OF THE |
| | CONNECTED LOAD. |
| | 4. YOU SHALL INDICATE THE FOLLOWING WITH EITHER A NOTE |
| | OR SHOWN ON THE PLANS: |
| | ALL OUTDOOR RECEPTACLES SHALL BE RATED AS WEATHER |
| | RESISTANT AS PER NEC 406.8 |
| | ALL RECEPTACLES SHALL BE TAMPER RESISTANT AS PER NEC |
| | 406.11 |
| | ARC-FAULT PROTECTION IS REQUIRED AS PER NEC 210.12 |
| | LIGHTING OUTLET BOXES IN THE CEILING SHALL BE CAPABLE |
| | OF SUPPORTING 50#'S AS PER NEC 314.27 |
| | 5. BEDROOM HALL SMOKE DETECTOR SHALL ALSO BE CAPABLE OF |
| | DETECTING HIGH LEVELS OF CO (CARBON MONOXIDE) AS PER |
| | FBC-R 315. |
| | 6.RELOCATE THE LIGHT OUTLET AT THE REAR DOORS SO AS NOT |
| | TO BLOCK IT BEHIND THE DOOR. |
| | 7. OUTLETS SPACING THROUGHOUT ALL HABITABLE ROOMS SHALL |
| | BE AS INDICATED BY NEC 210.52(A) |
| | 8. OUTLETS ALONG THE KITCHEN COUNTER SHALL BE AS PER |
| | NEC 210.52(C) |
| | 9. MASTER BATHROOM OUTLET SHALL BE AS INSTRUCTED BY NEC |
| | 210.52(D) |
| | 10. THE MASTER BEDROOM CORRIDOR IS MISSING AN OUTLET AS |
| | PER NEC 210.52(H) |
| | 11. CLARIFY THE DELTA 1 CLOUD WITH REGARDS TO WHAT USED |
| | TO BE HVAC EQUIPMENT IN THE FIRST REVIEW. KEEPING IN |
| | MIND THAT NEC 110.33(B) HAS SPECIFIC REQUIREMENTS WHICH |
| | SHALL BE ADDRESSED/CONSIDERED. |
| | |
| | FOR QUESTIONS, PLEASE CONTACT MIKE ALBARRAN |
| | CITY OF WEST PALM BEACH ELECTRICAL PLANS EXAMINER |
| | [email protected] |