Plan Review Notes
Plan Review Notes For Permit 15040129
Permit Number 15040129
Review Stop M
Sequence Number 1
Notes
Date Text
2015-05-18 14:58:061ST. MECHANICAL REVIEW. 5/18/15
  
 1) PROVIDE AC LOAD CALCULATIONS INCLUDING MANUAL J
 WORKSHEETS PER SECTION 403.6.1 FBC-10 ENERGY
 CONSERVATION.
 2) DESIGN CRITERIA: PROVIDE A LIST OF APPLICABLE CODES
 AND STANDARDS USED IN THE DESIGN OF THE PROJECT. SEE
 FBC-10 RESIDENTIAL, AND
 FBC-10 EXISTING BUILDING CODE. PLACE THE LEVEL OF
 ALTERATION ON THE PLANS.
 3) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH
 SECTION 711 FBC-10 EXISTING BUILDING, AND TABLE 104.4.1
 FBC-10 ENERGY.
 PLEASE NOTE THAT THE PLAN INDICATES NEW AC CONDITIONING
 IN THE GARAGE WHICH WILL DEFINE THE AREA AS AN ADDITION
 PER SECTION 202.
 THIS AREA MUST NOW MEET THE CURRENT CODE FOR THE
 THERMAL ENVELOPE (WALL AND CEILING INSULATIONS), WINDOW
 AND DOOR U-VALUES AND SHGC, ETC.
 4) SHEET 8.0: UPDATE THE CODE SECTION FOR CU TIE DOWN
 IN COMPLIANCE WITH SECTION M1307.2.1 FBC-10
 RESIDENTIAL.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  