| Notes |
| Date |
Text |
| 2015-05-18 14:58:06 | 1ST. MECHANICAL REVIEW. 5/18/15 | | | | | | 1) PROVIDE AC LOAD CALCULATIONS INCLUDING MANUAL J | | | WORKSHEETS PER SECTION 403.6.1 FBC-10 ENERGY | | | CONSERVATION. | | | 2) DESIGN CRITERIA: PROVIDE A LIST OF APPLICABLE CODES | | | AND STANDARDS USED IN THE DESIGN OF THE PROJECT. SEE | | | FBC-10 RESIDENTIAL, AND | | | FBC-10 EXISTING BUILDING CODE. PLACE THE LEVEL OF | | | ALTERATION ON THE PLANS. | | | 3) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH | | | SECTION 711 FBC-10 EXISTING BUILDING, AND TABLE 104.4.1 | | | FBC-10 ENERGY. | | | PLEASE NOTE THAT THE PLAN INDICATES NEW AC CONDITIONING | | | IN THE GARAGE WHICH WILL DEFINE THE AREA AS AN ADDITION | | | PER SECTION 202. | | | THIS AREA MUST NOW MEET THE CURRENT CODE FOR THE | | | THERMAL ENVELOPE (WALL AND CEILING INSULATIONS), WINDOW | | | AND DOOR U-VALUES AND SHGC, ETC. | | | 4) SHEET 8.0: UPDATE THE CODE SECTION FOR CU TIE DOWN | | | IN COMPLIANCE WITH SECTION M1307.2.1 FBC-10 | | | RESIDENTIAL. | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|