| 2015-05-18 13:15:20 | ELECTRICAL PLAN REVIEW |
| | |
| | FIRST REVIEW FAILED AS INDICATED BELOW: |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED TO THE |
| | ELECTRICAL SUBMITTAL FOR A SATISFACTORY ELECTRICAL |
| | REVIEW: |
| | |
| | 1. YOU SHALL PROVIDE LOAD CALC FOR THE NEW LOAD CENTER. |
| | 2. YOU SHALL PROVIDE A PANEL SCHEDULE FOR THE NEW LOAD |
| | CENTER. |
| | 3. INDICATE THE FEEDERS CONDUCTORS FOR THE NEW LOAD |
| | CENTER. SHALL BE IN ACCORDANCE TO THE RESULTS OF THE |
| | CONNECTED LOAD. |
| | 4. INDICATE IF THE NEW LOAD CENTER IS GOING TO HAVE A |
| | MAIN BREAKER OR WILL IT BE A MAIN LUG ONLY THEREFORE |
| | THE MAIN TO BE IN THE MAIN PANEL. IN SUCH CASE THE |
| | FEEDERS TO THE MAIN PANEL SHALL BE SUFFICIENT TO CARRY |
| | THE ADDED LOAD. |
| | 5. ALL CENTRAL VACUUM CLEANER OUTLETS TO BE AS MANDATED |
| | BY NEC 422.15 |
| | 6. ALL OUTDOOR RECEPTACLES SHALL BE RATED AS WEATHER |
| | RESISTANT AS PER NEC 406.8 |
| | 7. ALL RECEPTACLES SHALL BE TAMPER RESISTANT AS PER |
| | NE#C 406.11 |
| | 8. ARC-FAULT PROTECTION IS REQUIRED AS PER NEC 210.12 |
| | 9. BEDROOM HALL SMOKE DETECTOR SHALL ALSO BE CAPABLE OF |
| | DETECTING HIGH LEVELS OF CO (CARBON MONOXIDE) AS PER |
| | FBC-R 315. |
| | 10.RELOCATE THE LIGHT OUTLET AT THE REAR DOORS SO AS |
| | NOT TO BLOCK IT BEHIND THE DOOR. |
| | 11. LIGHTING OUTLET BOXES IN THE CEILING SHALL BE |
| | CAPABLE OF SUPPORTING 50#'S AS PER NEC 314.27 |
| | 12. TELEPHONE AND TV COMMUNICATION BOXES, THOUGH NOT |
| | INDICATED ON THE PLANS, SHALL BE PROVIDED WITH ADEQUATE |
| | LIGHTING AS INDICATED IN NEC 210.70(3) |
| | 13. OUTLETS SPACING THROUGHOUT ALL HABITABLE ROOMS |
| | SHALL BE AS INDICATED BY NEC 210.52(A) |
| | 14. OUTLETS ALONG THE KITCHEN COUNTER SHALL BE AS PER |
| | NEC 210.52(C) |
| | 15. MASTER BATHROOM OUTLET SHALL BE AS INSTRUCTED BY |
| | NEC 210.52(D) |
| | 16. THE MASTER BEDROOM CORRIDOR IS MISSING AN OUTLET AS |
| | PER NEC 210.52(H) |
| | |
| | FOR QUESTIONS, PLEASE CONTACT MIKE ALBARRAN |
| | CITY OF WEST PALM BEACH ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | |