Plan Review Notes
Plan Review Notes For Permit 15040129
Permit Number 15040129
Review Stop B
Sequence Number 1
Notes
Date Text
2015-05-15 16:58:42RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 103.2.1 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- PLANS SUBMITTED NEED THE ENGINEER'S SEAL AND
 ORIGINAL SIGNATURE AS REQUIRED BY CHAPTER 471 F.S.
  
 3- THE OWNER OF THE HOUSE IS A TRUST. IT DOESN'T
 QUALIFY AS OWNER/BUILDER. NEED CONTRACTOR TO APPLY FOR
 THE PERMITS. CHAPTER 489 F.S.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR,MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONALS FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE VALUATION AS REQUIRED OR PROVIDE
 COPY OF SIGNED CONTRACTS THAT INCLUDE ALL LABOR AND
 MATERIALS, INCLUDING THE DESIGN PROFESSIONALS FEES.
  
 5- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 6- THE PROJECT NAME SHOWN ON PLANS SUBMITTED IS
 CHAMBERS RESIDENCE. THIS DOESN'T MATCH THE NAME OF THE
 OWNER. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 7- SHEET 3.0 SPECIFIES REMOVAL OF WINDOWS AND DOORS.
 CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 (SPECIALLY THE BEDROOM WINDOWS) TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 604 OF 2010
 FBC-EXISTING BUILDING.
  
 8- AREA TABULATION SHOWN ON SHEET 2.0 DOESN'T MATCH
 AREAS SHOWN ON SHEET 5.0. PROVIDE CORRECT AREAS FOR A/C
 AREA, GARAGE, STORAGE, ETC. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WOOD ENTRY DOOR AS SHOWN ON PLANS.
  
 B) DINING ROOM EXTERIOR DOOR AS SHOWN ON PLANS..
  
 C) STORAGE DOUBLE DOOR AS SHOWN ON PLANS.
  
 D) GARAGE OVERHEAD DOOR SIZE AS SPECIFIED ON PLANS.
  
 E) SINGLE HUNG WINDOWS.
  
 F) FIXED WINDOWS.
  
 G) ROOF SHINGLES.
  
 H) PEEL AND STICK SHINGLES UNDERLAYMENT SPECIFIED ON
 PLANS.
  
 I) MODIFIED BITUMEN FOR THE FLAT ROOF. AND CLEARLY
 IDENTIFY APPROVED ASSEMBLY. ALSO, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF 2010 FBC-RESIDENTIAL.
  
 J) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS AND ALL DETAILS. NOTE: PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO THE SPECIFIED CONNECTOR.
  
 K) HARDIE BOARD SIDING AS SPECIFIED ON PLANS.
  
 L) HARDIE SOFFIT AS SPECIFIED ON PLANS.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11 - SHEET 4.1:
 A) WHERE ARE DETAILS S1/4.2, S2/4.2, S3/4.2 AND S4/4.2
 THAT ARE KEYED ON THE FOUNDATION PLAN?. SEC. 107.2.1
 CITY AMENDMENTS.
  
 B) SIZE OF STEEL COLUMN BASE PLATE SHOWN ON DETAIL
 F5/4.1 DOESN'T MATCH SIZE SPECIFIED ON COLUMN/BASE
 PLATE SCHEDULE. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 C) DETAIL F2/4.1: SIMPSON SP6 CONNECTOR DOESN'T WORK
 FOR A 2X4 WOOD STUD. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 12- SPECIFY GUTTERS WITH DOWNSPOUTS AS REQUIRED BY SEC.
 R318.6 OF 2010 FBC-RESIDENTIAL.
  
 13- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 ROOF CROSS VENTILATION AS REQUIRED BY SEC. R806 OF 2010
 FBC-RESIDENTIAL FOR PITCHED AND FLAT ROOFS. IF
 DESIGNING UNVENTED ATTIC , THEN PROVIDE COMPLETE
 SPECIFICATIONS. SEC. R806.4
  
 14- PROVIDE GARAGE DOOR STRUCTURAL BUCK DETAIL. SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 15- WALL SECTIONS ON SHEET 4.2 SHOW R16 AND R19 WALL
 INSULATION. REVISE AS REQUIRED. COORDINATE WITH THE
 ENERGY CALCULATIONS. ALSO, TAKE INTO CONSIDERATION THAT
 R19 BATT INSULATION DOESN'T FIT ON A 2X6 WALL. SEC.
 107.2.1 CITY AMENDMENTS.
  
 16- WOOD TRUSS DESIGN LOADS ON SHEET 4.3: SPECIFY THE
 ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2010
 FBC-RESIDENTIAL.
  
 17- SPECIFY ATTIC ACCESS AT GARAGE WING AS REQUIRED BY
 SEC. R807 OF 2010 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE AND REMOVE ANY REVISED SHEET.
  