| 2015-05-15 16:58:42 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 103.2.1 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 2- PLANS SUBMITTED NEED THE ENGINEER'S SEAL AND |
| | ORIGINAL SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. |
| | |
| | 3- THE OWNER OF THE HOUSE IS A TRUST. IT DOESN'T |
| | QUALIFY AS OWNER/BUILDER. NEED CONTRACTOR TO APPLY FOR |
| | THE PERMITS. CHAPTER 489 F.S. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR,MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| | PROFESSIONALS FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. REVISE VALUATION AS REQUIRED OR PROVIDE |
| | COPY OF SIGNED CONTRACTS THAT INCLUDE ALL LABOR AND |
| | MATERIALS, INCLUDING THE DESIGN PROFESSIONALS FEES. |
| | |
| | 5- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 6- THE PROJECT NAME SHOWN ON PLANS SUBMITTED IS |
| | CHAMBERS RESIDENCE. THIS DOESN'T MATCH THE NAME OF THE |
| | OWNER. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 7- SHEET 3.0 SPECIFIES REMOVAL OF WINDOWS AND DOORS. |
| | CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS |
| | (SPECIALLY THE BEDROOM WINDOWS) TO VERIFY COMPLIANCE |
| | WITH THE EGRESS REQUIREMENTS OF SEC. 604 OF 2010 |
| | FBC-EXISTING BUILDING. |
| | |
| | 8- AREA TABULATION SHOWN ON SHEET 2.0 DOESN'T MATCH |
| | AREAS SHOWN ON SHEET 5.0. PROVIDE CORRECT AREAS FOR A/C |
| | AREA, GARAGE, STORAGE, ETC. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) WOOD ENTRY DOOR AS SHOWN ON PLANS. |
| | |
| | B) DINING ROOM EXTERIOR DOOR AS SHOWN ON PLANS.. |
| | |
| | C) STORAGE DOUBLE DOOR AS SHOWN ON PLANS. |
| | |
| | D) GARAGE OVERHEAD DOOR SIZE AS SPECIFIED ON PLANS. |
| | |
| | E) SINGLE HUNG WINDOWS. |
| | |
| | F) FIXED WINDOWS. |
| | |
| | G) ROOF SHINGLES. |
| | |
| | H) PEEL AND STICK SHINGLES UNDERLAYMENT SPECIFIED ON |
| | PLANS. |
| | |
| | I) MODIFIED BITUMEN FOR THE FLAT ROOF. AND CLEARLY |
| | IDENTIFY APPROVED ASSEMBLY. ALSO, PROVIDE SIGNED AND |
| | SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301 |
| | OF 2010 FBC-RESIDENTIAL. |
| | |
| | J) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | FRAMING PLANS AND ALL DETAILS. NOTE: PROVIDE ONLY THE |
| | FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING |
| | THE SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT |
| | APPROVAL NUMBER NEXT TO THE SPECIFIED CONNECTOR. |
| | |
| | K) HARDIE BOARD SIDING AS SPECIFIED ON PLANS. |
| | |
| | L) HARDIE SOFFIT AS SPECIFIED ON PLANS. |
| | |
| | 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 11 - SHEET 4.1: |
| | A) WHERE ARE DETAILS S1/4.2, S2/4.2, S3/4.2 AND S4/4.2 |
| | THAT ARE KEYED ON THE FOUNDATION PLAN?. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | B) SIZE OF STEEL COLUMN BASE PLATE SHOWN ON DETAIL |
| | F5/4.1 DOESN'T MATCH SIZE SPECIFIED ON COLUMN/BASE |
| | PLATE SCHEDULE. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | C) DETAIL F2/4.1: SIMPSON SP6 CONNECTOR DOESN'T WORK |
| | FOR A 2X4 WOOD STUD. REVISE AS REQUIRED. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 12- SPECIFY GUTTERS WITH DOWNSPOUTS AS REQUIRED BY SEC. |
| | R318.6 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 13- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | ROOF CROSS VENTILATION AS REQUIRED BY SEC. R806 OF 2010 |
| | FBC-RESIDENTIAL FOR PITCHED AND FLAT ROOFS. IF |
| | DESIGNING UNVENTED ATTIC , THEN PROVIDE COMPLETE |
| | SPECIFICATIONS. SEC. R806.4 |
| | |
| | 14- PROVIDE GARAGE DOOR STRUCTURAL BUCK DETAIL. SEC. |
| | R301.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 15- WALL SECTIONS ON SHEET 4.2 SHOW R16 AND R19 WALL |
| | INSULATION. REVISE AS REQUIRED. COORDINATE WITH THE |
| | ENERGY CALCULATIONS. ALSO, TAKE INTO CONSIDERATION THAT |
| | R19 BATT INSULATION DOESN'T FIT ON A 2X6 WALL. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 16- WOOD TRUSS DESIGN LOADS ON SHEET 4.3: SPECIFY THE |
| | ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 17- SPECIFY ATTIC ACCESS AT GARAGE WING AS REQUIRED BY |
| | SEC. R807 OF 2010 FBC-RESIDENTIAL. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE REPLACE AND REMOVE ANY REVISED SHEET. |
| | |