| Plan Review Notes For Permit 15040128 |
| Permit Number |
15040128 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-19 14:02:22 | 1ST. MECHANICAL REVIEW | | | WPB AMENDMENTS TO FBC-10 BUILDING. | | | | | | 1) PURSUANT TO SECTION 909.1 FBC-10 EXISTING BUILDING | | | CODE, PROVIDE VENTILATION CALCULATIONS FOR THE NEW | | | TENANT BUILDINGS PER TABLE 404.3 FMC-10. | | | DUE TO THE CHANGE IN USE, VERIFICATION THAT THE | | | EXISTING AC AND EXHAUST SYSTEMS ARE ADEQUATELY SIZED | | | FOR THE NEW OPERATIONS IS REQUIRED. |
|