| Plan Review Notes For Permit 15040128 |
| Permit Number |
15040128 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-14 14:35:32 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | PROVIDE AN ELECTRICAL PLAN WITH THE FOLLOWING: | | | ELECTRICAL RISER PLAN SHOWING ALL FEEDERS, DISCONNECTS | | | AND PANEL BOARDS | | | LOCATION OF THE ELECTRICAL SERVICE AND MAIN | | | DISCONNECTS | | | LOCATION OF ALL ELECTRICAL PANELBOARDS | | | SAFE WORKING SPACE AT ELECTRICAL DISCONNECTS AND | | | PANELBOARDS | | | EXIT AND EMERGENCY ILLUMINATION | | | | | | PROVIDE ELECTRIC NOTES ON THE PLAN INDICATING THE | | | FOLLOWING: | | | GENERAL PURPOSE RECEPTACLES INSTALLED IN THE | | | BATHROOMS, KITCHENS, ROOFTOPS, OUTDOORS, WITHIN SIX | | | FEET OF SINKS,AT ELECTRIC DRINKING FOUNTAINS, AND | | | VENDING MACHINES ARE GFCI PROTECTED. | | | ALL DISCONNECTS SHALL BE LEGIBLY MARKED TO INDICATE | | | THEIR PURPOSE. | | | | | | CODE REFERENCES: | | | FBC EXISTING BUILDING 908.2, 908.3, 908.4 | | | NEC 110.22, 110.26, 210. 8, 215.5, 422.51, 422.52 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-373-3701 | | | |
|