| 2015-05-05 10:25:42 | APPROVED WITH EXCEPTION. |
| | THE PLANS HAVE BEEN APPROVED PROVISIONALLY. THE |
| | FOLLOWING DEFICIENCIES SHALL BE VERIFIED TO BE CODE |
| | COMPLIANT BY THE ELECTRICAL INSPECTOR ON SITE. |
| | FAILURE TO CORRECT THE LISTED DEFICIENCIES PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | |
| | 1) THE FAULT CURRENT CALCULATION ON SHEET E-0 INDICATES |
| | A 22,000AMP AIC MIN RATING IS REQUIRED AT THE SERVICE |
| | EQUIPMENT. HOWEVER THE PANELS INDICATE A MINIMUM OF |
| | ONLY10,000AMPS. |
| | |
| | 2) THE LOAD SUMARY IS IN CONFLICT WITH THE TOTAL |
| | CONNECTED LOADS INDICATED IN THE PANEL SCHEDULES. LOADS |
| | FOR NEW CIRCUITS OR EXTENDED CIRCUITS IN PREVIOUSLY |
| | WIRED DWELLING UNITS SHALL BE CALCULATED IN ACCORDANCE |
| | WITH 220.12 OR 220.14, NEC 220.16(2) |
| | |
| | 3) VERIFY THE WORKING CLEARANCES FOR ELECTRICAL PNAEL |
| | "A" ARE IN COMPLIANCE WITH THE NEC 110.26 |
| | |
| | 4) VERIFY COMPLIANCE WITH THE LUMINAIRES IN THE CLOTHES |
| | CLOSETS. THE NEC STATES LUMINAIRES SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) |
| | AND (B). |
| | |
| | 5) VERIFY THE FLOOR BOXES ARE DESIGNED SPECIFICALLY FOR |
| | USE IN THIS APPLICATION. "BOXES LISTED SPECIFICALLY FOR |
| | THIS APPLICATION SHALL BE USED FOR RECEPTACLES LOCATED |
| | IN THE FLOOR." NEC 314.27(C) |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |