2015-05-05 10:25:42APPROVED WITH EXCEPTION.
 THE PLANS HAVE BEEN APPROVED PROVISIONALLY. THE
 FOLLOWING DEFICIENCIES SHALL BE VERIFIED TO BE CODE
 COMPLIANT BY THE ELECTRICAL INSPECTOR ON SITE.
 FAILURE TO CORRECT THE LISTED DEFICIENCIES PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) THE FAULT CURRENT CALCULATION ON SHEET E-0 INDICATES
 A 22,000AMP AIC MIN RATING IS REQUIRED AT THE SERVICE
 EQUIPMENT. HOWEVER THE PANELS INDICATE A MINIMUM OF
 ONLY10,000AMPS.
  
 2) THE LOAD SUMARY IS IN CONFLICT WITH THE TOTAL
 CONNECTED LOADS INDICATED IN THE PANEL SCHEDULES. LOADS
 FOR NEW CIRCUITS OR EXTENDED CIRCUITS IN PREVIOUSLY
 WIRED DWELLING UNITS SHALL BE CALCULATED IN ACCORDANCE
 WITH 220.12 OR 220.14, NEC 220.16(2)
  
 3) VERIFY THE WORKING CLEARANCES FOR ELECTRICAL PNAEL
 "A" ARE IN COMPLIANCE WITH THE NEC 110.26
  
 4) VERIFY COMPLIANCE WITH THE LUMINAIRES IN THE CLOTHES
 CLOSETS. THE NEC STATES LUMINAIRES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A)
 AND (B).
  
 5) VERIFY THE FLOOR BOXES ARE DESIGNED SPECIFICALLY FOR
 USE IN THIS APPLICATION. "BOXES LISTED SPECIFICALLY FOR
 THIS APPLICATION SHALL BE USED FOR RECEPTACLES LOCATED
 IN THE FLOOR." NEC 314.27(C)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]