 PROJECT: 312 BARCELONA
 PERMIT#: 15040124
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1STELECTRICAL PLAN REVIEW OF REVISION #15040124
 ACTION: DENIED
  
 DUPLICATE COMMENTS:
  
 1) PROVIDE A REVISED FLOOR PLAN INDICATING THE
 ELECTRICAL SERVICE AND EACH OF THE PANEL LOCATIONS. THE
 RISER INDICATES PANEL "B" IS A PART OF THE SERVICE
 ENTRANCE SWITCHGEAR HOWEVER THE PANEL SCHEDULE FOR
 PANEL "B" INDICATES THE LOCATION BEING IN THE LAUNDRY
 ROOM. PLEASE CLARIFY THIS. WPB AMENDMENTS TO FBC
 107.3.2
  
 2) FULL SIZE FEEDERS ARE REQUIRED TO FEED PANELS A AND
 B. NEC 210.15(B)(6)
 "FOR APPLICATION OF THIS SECTION, THE MAIN POWER FEEDER
 SHALL BE THE FEEDER BETWEEN THE MAIN DISCONNECT AND THE
 PANELBOARD THAT SUPPLIES, EITHER BY BRANCH CIRCUITS OR
 BY FEEDERS, OR BOTH, ALL LOADS THAT ARE PART OR
 ASSOCIATED WITH THE DWELLING UNIT."
  
 3) PROVIDE A PANEL SCHEDULE FOR EACH OF THE PANELS ON
 THE RISER DIAGRAM. NEC 215.5
  
 4) PROVIDE A LOAD CALCULATION FOR THE SERVICE. NEC
 220.16
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  