Plan Review Notes
Plan Review Notes For Permit 15040124
Permit Number 15040124
Review Stop E
Sequence Number 1
Notes
Date Text
2015-04-13 12:50:014/13/2015
 PROJECT: 312 BARCELONA
 PERMIT#: 15040124
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1STELECTRICAL PLAN REVIEW OF REVISION #15040124
 ACTION: DENIED
  
 1) REVISE RISER DIAGRAM FOR CLARIFICATION. IT APPEARS
 FROM THE ONLY TWO PANEL SCHEDULES PROVIDED THAT THERE
 ARE ONLY 2 PANELS INSTALLED. HOWEVER THE RISER
 INDICATES THE USE OF A 400A COMBINATION METER/MAIN WITH
 PANEL "B" INCLUDED WITH A 400AMP RATED BUSS AND TWO
 200A MAINS? ONE FEEDING PANEL "A" AND THE OTHER FEEDING
 PANEL "B1". PLEASE CLARIFY IS THERE A B1? OR ONLY A AND
 B EACH FED FROM A 200AMP MAIN?
  
 2) IF THERE IS A PANEL B1 PROVIDE THE FEEDER SIZE, A
 PANEL SCHEDULE AND THE LOCATION. THERE IS A SUB-FEED
 LUG KIT INDICATED IN PANEL SCHEDULE "A" IS THIS
 SUPPOSED TO FEED PANEL "A1"?
  
 3) PROVIDE A REVISED FLOOR PLAN INDICATING THE
 ELECTRICAL SERVICE AND EACH OF THE PANEL LOCATIONS. THE
 RISER INDICATES PANEL "B" IS A PART OF THE SERVICE
 ENTRANCE SWITCHGEAR HOWEVER THE PANEL SCHEDULE FOR
 PANEL "B" INDICATES THE LOCATION BEING IN THE LAUNDRY
 ROOM. PLEASE CLARIFY THESE
  
 4) FULL SIZE FEEDERS ARE REQUIRED TO FEED PANELS A AND
 B. NEC 210.15(B)(6)
 "FOR APPLICATION OF THIS SECTION, THE MAIN POWER FEEDER
 SHALL BE THE FEEDER BETWEEN THE MAIN DISCONNECT AND THE
 PANELBOARD THAT SUPPLIES, EITHER BY BRANCH CIRCUITS OR
 BY FEEDERS, OR BOTH, ALL LOADS THAT ARE PART OR
 ASSOCIATED WITH THE DWELLING UNIT."
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  