2015-06-10 07:23:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040122
 ADD: 525 S. FLAGLER DR. SUITE # 29A/B
 CONT: R & D CONSTRUCTORS
 TEL: (561)889-1751
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JUNE 12/ 2015
 ACTION: PROVISO
  
 1) RED LINED!!!! SHEET A-101.00 DOOR SCHEDULE, DOORS
 D02 & D03 INDICATE THEY ARE BOTH 2'-6" DOORS. UNDER THE
 2010 FBC-B1008.1.1 THE MINIMUM SIZE SHALL BE 32 INCHES
 CLEAR WIDH, MINIMUM SIZE FOR A SWING DOOR IS 2 FT 10
 INCHES, EXCEPTION # 1 THE MINIMUM AND MAXIMUM WIDTH
 SHALL NOT APPLY TO DOOR OPENINGS THAT ARE NOT PART OF
 THE REQUIRED MEANS OF EGRESS IN GROUP R-2 AND R-3
 OCCUPANCIES. THESE DOORS ARE PART OF THE MEANS OF
 EGRESS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]