Plan Review Notes
Plan Review Notes For Permit 15040122
Permit Number 15040122
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-04-27 15:44:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET G 101, PROVIDE NOTES INDICATING; THE PROPOSED
 PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH EDITION
 OF FLORIDA FIRE PREVENTION CODE INCLUDING THE 2012
 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER APPLICABLE
 CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) SHEET G101, PROVIDE A HORIZONTAL FRONT VIEW DRAWING
 OF THE FIRE PLACE UNIT INDICATING DIMENSIONS OF STEEL
 WALL AND TO NEAREST COMBUSTIBLES.
  
 3) SHEET G101, PROVIDE A NOTE, THE NATURE OF THE
 REMODEL REQUIRES AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 4) ADDRESS BUILDING COMMENTS.
  
 5) ADDITIONALL COMMENTS MAY BE GENERATED ON REVIEW OF
 THE PROVIDED ADDITIONAL INFORMATION NOTED ABOVE.
  