| Plan Review Notes For Permit 15040056 |
| Permit Number |
15040056 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-07 16:08:08 | THE FOLLOWING ITEMS NEED ATTEN/CORRECTION FOR A | | | SUCCESSFUL REVIEW: | | | PG. E1.1 | | | 1. EVEN IF AS EXISTING, THE LIFE SAFETY ILLUMINATION | | | SHALL BE SHOWN ON THE PLANS TO VERIFY COMPLIANCE | | | 2, OFFICE RM 409 IS MISSING AN EXIT SIGN ABOVE THE DOOR | | | AS WELL AS EMERGENCY LIGHTING INSIDE THE ROOM. AS PER | | | NEC700.16, THERE CANT BE A ROOM LEFT IN TOTAL DARKNESS | | | IN THE EVEN OF A POWER FAILURE. | | | PG. E1.2 | | | 1. ACCORDING TO THE NOTES, THE AREA ABOVE THE CEILING | | | IS ALL A PLENUM, MAKE CERTAIN THAT THE NEW TRANSFORMER | | | INDICATED ABOVE THE CEILING IT THE IT ROOM IS LISTED | | | FOR A PLENUM. | | | PG. E2.1 | | | 1. VENDING MACHINES AND/OR THEIR CIRCUIT SHALL COMPLY | | | WITH NEC422..51 | | | 2. NEW PANEL "LC" AS WELL AS ALL EXISTING, SHALL BEAR | | | THE REQUIRED FLASH PROTECTION DECAL AS INDICATED IN | | | NEC110.16 | | | 3. THE RISER DIAGRAM IS NOT COMPLETE. THE RISER DIAGRAM | | | SHALL INCLUDE IN ADDITION TO ALL THE EXISTING LOADS, | | | THE STANDBY GENERATOR AS WELL. |
|