| Plan Review Notes For Permit 15040052 |
| Permit Number |
15040052 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-07 17:08:36 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PROJECT HAS A 25' MRH, A 5/12 SLOPED ROOF AND IS | | | LOCATED IN EXPOSURE C IN A 170 MPH VULT WIND ZONE. THE | | | REQUIRED UPLIFT MOMENT FOR THE ROOF TILE (FIELD) IS | | | 35.9 FT-LB F AND THE ATTACHMENT SPECIFIED IN THE | | | PRODUCT APPROVAL FOR THE 'S' TILE (NOA NO. 12-0210.01) | | | HAS AN ATTACHMENT RESISTANCE OF 28.5 FT-LB F. |
|