| 2015-04-03 14:53:16 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | 1) NOTIFICATION IS BEING REMOVED FROM THE CENTER, LARGE | | | ROOM AND RELOCATED. NOTIFICATION IS REQUIRED IN THAT | | | ROOM, OR PROVIDE CODE JUSTIFICATIOIN FOR NOT PROVIDING | | | IT. | | | | | | 2) A NOTIFICATION DEVICE IS NOT INDICATED IN THE SIDE | | | BATHROOM. | | | | | | 3) A SMOKE DETECTOR IS NOT INDICATED ABOVE THE FACP. | | | | | | 4) THE FACP ROOM DOOR SHALL HAVE A SIGN INSTALLED THAT | | | READS "FACP". | | | | | | THE FIRE INSPECTOR SHALL FIELD VERIFY THE ABOVE AT THE | | | TIME OF FIRE INSPECTION AND BEFORE ISSUING THE FIRE | | | FINAL. | | | | | | | | | |
|