| 2015-07-01 09:07:32 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15040016 |
| | ADD: 701 N. ROSEMARY AVE. |
| | CONT: ADVANCED CONSTRUCTION |
| | TEL: (561)262-6037 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: WED. JULY 01/2015 |
| | ACTION: DENIED |
| | |
| | NOTICE !!!!!! ONLY (1) SET OF PLANS WERE RESUBMITTED |
| | !!!!!!! |
| | |
| | 1) COMPLIED. |
| | |
| | |
| | 2) BUILDING PROVISO: PLANS RED LINED FOR ACCESSIBILITY. |
| | SHEET AD103 TO MEET W. P. B. CITY STANDARD OF DOUBLE |
| | STRIPING SEE W.P. B. MUNI CODE SECTION 94-485. |
| | |
| | 3) COMPLIED. ACCESSIBLE ACCESS AISLE AND WLKWAY TO |
| | ACCESSIBLE ENTRY. |
| | |
| | 4) COMPLIED> PLANS DO NOT INDICATE COMPLIANCE WITH 2010 |
| | FL ACCESS. CODE 904.4 SALES AND SERVICE COUNTERS. |
| | SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH |
| | 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE |
| | COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR |
| | SERVICE COUNTER TOP. |
| | |
| | 5) COMPLIED.WIND DESIGN CRITERIA |
| | |
| | 6A) 3RD REQUEST. SHEET AD201 HAS A CHANGE IN WINDOW |
| | STYLE, THE LAST SUBMITTAL THE FRONT ELEVAION INDICATED |
| | THE USE OF PGT SERIES PW 3020 PICTURE WINDOWS, |
| | SUBMITTED NOA 12-0516.05. THIS SUBMITTAL SHEET AD201 |
| | THE FRONT ELEVATION NOW SHOWS STOREFRONT WINDOW SYSTEM. |
| | THE SUBMITTED NOA US ALUMINUM NOA # 14-0331.02 HAS NOT |
| | BEEN REVIEWED BY THE DESIGNER OF RECORD. |
| | |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6B)COMPLIED. |
| | |
| | 7) NOT APPLICABLE NO NEW ROOF SYSTEM. |
| | |
| | 8) PROVISO: A REVISION MAYBE NECESSARY TO SHOW |
| | ADDITIONAL DETAILS. SHEET AS201 SHOW DETAIL 2 OOF |
| | FRAMING FOR THE SIDEWALL & NEW ROOF. THIS DETAIL FAILS |
| | TO PROVIDE THE CONNECTION TO THE EXISTING ROOF FRAMING, |
| | DOES THE EXISTING LAST FRAMING MEMBER GET DOUBLED? DOES |
| | THIS FRAMING MEMBER REQUIRE ADDITIONAL STAPPING FOR THE |
| | ADDITIONAL UPLIFT OF A LARGER TRIBUTARY AREA AND BEING |
| | PART OF THE MWFRS? |
| | |
| | 9) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |