| Plan Review Notes For Permit 15040016 |
| Permit Number |
15040016 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-05-09 07:36:28 | 1) THE INSIDE MINIMUM WIDTH OF THE ACCESSIBLE TOILET | | | ROOM SHALL BE 85 INCHES IF BUILT PERFECT. 86 INCHES | | | ALLOWS FOR TOLERANCES. FAC SECS.604.3.1, 606.2 & 305. | | | 2) SUBMIT A WATER AND SANITARY RISER DIAGRAM FOR THE | | | RELOCATION OF THE PLUMBING FIXTURES IN BOTH TOILET | | | ROOMS. WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3. | | | 3) THE SANITARY RISER ON SHT.AP 201 SHOWS A BATHTUB. | | | THE RISER IS NOT FOR THIS PROJECT. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|