| 2015-04-27 14:37:56 | 1ST REVIEW: FBC 2010 | | | | | | PLEASE PROVIDE THE FOLLOWING ADDITIONAL INFORMATION: | | | | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL FOR EXISTING | | | SERVICE AND COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES | | | AND SHOW CIRCUITS AND WIRING METHOD ON FLOOR PLAN. | | | | | | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. | | | | | | NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES | | | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE | | | BRANCH CIRCUITS. | | | | | | NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN | | | 25? OF MECHANICAL EQUIPMENT. | | | | | | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. | | | | | | NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE AUGMENTED | | | BY AN ADDITIONAL ELECTRODE 6FEET AWAY OR PROVIDE | | | EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|