2015-04-27 14:37:561ST REVIEW: FBC 2010
  
 PLEASE PROVIDE THE FOLLOWING ADDITIONAL INFORMATION:
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL FOR EXISTING
 SERVICE AND COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES
 AND SHOW CIRCUITS AND WIRING METHOD ON FLOOR PLAN.
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
  
 NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
  
 NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 25? OF MECHANICAL EQUIPMENT.
  
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
  
 NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE AUGMENTED
 BY AN ADDITIONAL ELECTRODE 6FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  