| Plan Review Notes For Permit 15031368 |
| Permit Number |
15031368 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-04-30 09:48:24 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE FIRE SPRINKLER HEADS ON BOTH SIDES OF THE GLASS | | | DOORS IS NOT APPROVED. THIS PROPOSED CONFIGURATION IS A | | | MISAPPLICATION OF A WATER CURTAIN FOR THIS | | | INSTALLATION. THIS DOOR PROTECTS THE ELEVATOR LOBBY AND | | | IS ALSO FUNCTIONING AS A REQUIRED EXIT. A 45 MINUTE | | | RATED GLASS DOOR(S) THAT IS(ARE) ALSO SEALED AND SMOKE | | | RATED FOR THE LOBBY IS REQUIRED. |
|