| 2015-04-02 13:02:04 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15031368 |
| | ADD: 625 N. FLAGLER DR. # 700 |
| | CONT: CHANDLIER CONSTRUCTION |
| | TEL: ( 561-791-6934 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE:THURS. APRIL 02/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET A-0.1 LIST THIS PROJECT AS A BUSINESS |
| | OCCUPANCY, THAT IT IS NOT A MIXED USE OCCUPANCY. THE |
| | SHEET DOES NOT HAVE THE OCCUPANCY SEPARATION CHECKED OR |
| | THE EXCEPTIONC CHECKED EITHER. SHEET A-2.1 SHOWS THE |
| | TENANTCY AS A SINGLE TENANT FULL FLOOR BUILD-OUT. THE |
| | FLOOR PLATE APPROXIMATELY 12,992 SQ. FT. OF BUSINESS |
| | OCCUPANCY. THE ROOMS NUMBERS IDENTIFIED AS 704,708,710 |
| | & 720 ARE ALL CONSIDERED A ASSEMBLY USAGE NOT BUSINESS. |
| | WHEN THE SQUARE FOOT AREAS ARE TOTALED TOGETHER(1,927 |
| | SQ. FT.) THEY ARE OVER THE 10 % OF THE FLOOR PLATE AND |
| | THE FLOOR PLATE BECOMES A MIXED USE OCCUAPANCY. |
| | |
| | 2010 FBC-B 08.2.1 AREA LIMITATIONS. AGGREGATE ACCESSORY |
| | OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 PERCENT OF |
| | THE BUILDING AREA OF THE STORY IN WHICH THEY ARE |
| | LOCATED AND SHALL NOT EXCEED THE TABULAR VALUES IN |
| | TABLE 503, WITHOUT BUILDING AREA INCREASES IN |
| | ACCORDANCE WITH SECTION 506 FOR SUCH ACCESSORY |
| | OCCUPANCIES. |
| | |
| | THE DESIGNER OF RECORD WILL NEED TO INDICATE THE DESIGN |
| | REQUIREMENTS AS EITHER COMPLYING WITH: |
| | FBC-B 508.3 NONSEPARATED OCCUPANCIES. BUILDINGS OR |
| | PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS |
| | OF THIS SECTION SHALL BE CONSIDERED AS NONSEPARATED |
| | OCCUPANCIES. |
| | OR |
| | FBC-B 508.4 SEPARATED OCCUPANCIES. BUILDINGS OR |
| | PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS |
| | OF THIS SECTION SHALL BE CONSIDERED AS SEPARATED |
| | OCCUPANCIES. |
| | |
| | 2) SHEET A2.2 SHOWS THE INSTALATION OF MARBLE AND TILE |
| | FLOORING. THE PLANS DO NOT INDICATE IF THERE IS A |
| | INTENT TO INSTALL A CRACK ISOLATION MEMBRANE BEFORE THE |
| | INSTALATION OF EITHER MARBLE OR TILE. IF SO THE CRACK |
| | ISOLATION MEMBRANE INSULATION WILL NEED TO COMPLY WITH |
| | FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | 3) SHEET A-2-1 THE CONFERENCE ROOM # 720, 1927 SQ. FT./ |
| | 15= 46 OCCUPANTS. SHEET A-3.1 THE DOOR SCHEDULE LIST |
| | THIS DOOR IDENTIED AS DOOR D4 AND A ALTERNATE SLIDING |
| | DOOR DESIGN. THE 2010 FBC-B 1008.1.2 DOES NOT ALLOW FOR |
| | SLIDDING DOORS AS A PART OF A MEANS OF EGRESS WHEN THE |
| | OCCUPANT LOAD IS GREATER THAN 10. |
| | |
| | 4) SHEET A-3.2 DETAIL # 05 SHOWS A ACCESSIBLE BREAK |
| | ROOM COUNTERAND SINK, THE PLANS DO NOT INDICATE |
| | COMPLIANCE WITH : 2010 FBC-ACCESSIBILITY CODE 606.3. |
| | HEIGHT. |
| | |
| | 5) SHEET A-4.1 DETAIL # 1 THE WOMENS RESTROOM THE NEW |
| | ACCESSIBLE TOLIET COMPARTMENT IS ONLY 7'-0" THIS WILL |
| | NOTE MEET THE REQUIREMENTS OF ACCESSIBILITY CODE |
| | 604.3.2. OVERLAP AND SIZE OF CLEARANCE AT WATER CLOSET. |
| | |
| | |